Product Data
355BAV Preferred
t
Plus 95i
95% AFUE Upflow Only Variable--Speed
Condensing Gas Furnace
Series C, Input Rates 60,000 thru 120,000 Btuh
A05085
Building
on
our
industry--leading
condensing
furnace
technology, the model 355BAV is our greatest innovation in
comfort control and operating efficiency.
Modern technology provides the Plus 95i
t
design with great
reliability, high efficiency, and ultra--quiet operation. Efficiencies
are above 95 percent Annual Fuel Utilization Efficiency (AFUE).
The model 355BAV Plus 95i
t
Condensing Gas Furnace
incorporates our patented Perfect Heat
t
Control. This control
interacts with a 2--stage gas valve, a variable--speed inducer
motor, and a variable--speed blower motor, allowing the Plus
95i
t
to adjust combustion air, firing rate, and airflow to maintain
peak efficiency throughout the operating cycle.
The Perfect Heat
t
system provides the ultimate in heating
comfort while minimizing electrical and gas consumption. The
Plus 95i also features Perfect Humidity control when combined
with a Bryant Thermidistat
t
Control and air conditioner or heat
pump system.
For even greater comfort and convenience, match the Plus 95i
furnace with a two--speed heat pump to create a HYBRID
HEAT
®
Dual Fuel system.
FEATURES
Perfect Heat
t
/Perfect Humidity
t
Control
—This intelligent
heating control constantly monitors operating conditions to adjust
for greater efficiency and comfort. The control operates 90% of
the time in low--heat and reserves the high--firing rate for times
when the heating demand is high. The Perfect Heat/Perfect
Humidity control has these additional features:
S
dedicated terminals for electrical connection of electronic air
cleaner and humidifier
S
adjustable blower off time
S
LED fault code display to aid in servicing
S
selectable airflow to match cooling unit
S
emergency heat setting
S
setting to increase airflow for bypass--type humidifier
S
selectable constant fan airflow
S
a multi--zone setting for use with zoned air distribution
systems a special dehumidification function increases cooling
comfort by providing greater humidity removal in summer
months
S
controls humidity even when there is no heating or cooling
demand
Three--Pass
Primary
Heat
Exchangers
—This
design
accelerates heat transfer and extracts heat that conventional heat
exchangers waste up the flue. The primary heat exchanger is
made of aluminized steel for corrosion resistance.
Flow--Through Secondary Heat Exchangers
—Each cell is
laminated with our patented Everlastic
t
polypropylene for
greater resistance to corrosion and is epoxy coated externally to
prevent oxidation. This breakthrough in heating technology
(Patent No. 4,738,307) helps extend the life of the furnace for
years of reliable performance. The heat exchangers are positioned
in the furnace to extract additional heat from the combustion
products regardless of furnace orientation.
Perfect Light
t
Igniter
—Bryant’s unique SiN igniter is not only
physically robust but it is also electrically robust. It is capable of
running at line voltage and does not require complex voltage
regulators as do other brands. This unique feature further
enhances the reliability of Bryant’s 355BAV gas furnace and
continues Bryant’s tradition of technology leadership and
innovation in providing a reliable and durable product.
Fan On Plus
t
—Improves comfort all year long by allowing
you to select the continuous fan speed right at the thermostat.
SmartEvap
t
—Allows your system to reduce summertime
humidity levels by nearly 10% over standard systems.
2
Upflow Only Design
—Allows the model 355BAV to be installed
in an upflow orientation only. Factory configured for upflow
applications. The model 355BAV is available in 5 heat/airflow
combinations.
Direct Venting
—This furnace can be installed as a 2--pipe/Direct
vent furnace.
2--Stage Gas Valve
—The 355BAV has a 2--stage gas valve to
vary the amount of gas being used from low--heat to high--heat
stage.
Fully--Insulated Casing
—Foil--faced insulation in the heat
exchanger section cuts the heat loss; double--density insulation in
the blower section reduces noise levels. The casing also has the
required openings for left-- or right--side connection of gas,
electric, drain, and vent connections.
Variable--Speed Motors
—Variable--speed operation improves
the comfort levels in the home. Variable--Speed motors are also
more economical to operate than standard motors. They have the
ability to adapt to changing conditions and provide consistent,
comfortable, and quiet heating. Motors and electronic controls are
covered by a 5--year limited warranty.
Sealed Combustion System
—This furnace brings in combustion
air from outside the furnace, which results in especially quiet
operation.
Monoport Inshot Burners
—Produce precise air--to--gas mixture
for clean burning. The large monoport on the inshot or injection
type burners seldom, if ever, needs cleaning.
Quality Registration
—The 355BAV is engineered and
manufactured under an ISO 9001 registered quality system.
Certifications
—The 355BAV units are CSA (A.G.A. and
C.G.A.) design certified for use with natural and propane gases,
as well as AHRI efficiency rating certified. The furnace is factory
shipped for use with natural gas. An CSA (A.G.A. and C.G.A.)
certified gas conversion kit is required to convert furnace for use
with propane gas. The model 355BAV meets California Air
Quality Management District emission requirements.
D E
S I G N
C
E R
T I F I E
D
CERTIFIED
Always Ask For
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
355B
A
V
3
DIMENSIONS
NO TES:
1. Minimum retur n-air openings at fur nace , based on metal duct. If fle x duct is used,
see fle x duct manuf acturerí s recommendations f or equiv alent diameters .
2. Minimum retur n-air opening at fur nace:
a. F or 800 CFM–16-in. (406mm) round or 14
1
/
2
(368 mm)x 12-in. (305 mm) rectangle
.
b. F or 1200 CFM–20-in. (508mm) round or 14
1
/
2
(368mm)x 19
1
/
2
-in. (495mm) rectangle
.
c. F or 1600 CFM–22-in. (559mm) round or 14
1
/
2
(368mm)x 23
1
/
4
-in. (591mm) rectangle
.
d. F or airflo w requirements abo v e 1800 CFM, see Air Deliv er y tab le in Product Data
literature f or specific use of single side inlets . The use of both side inlets , a
combination of 1 side and the bottom, or the bottom only will ensure adequate
retur n air openings f or airflo w requirements abo v e 1800 CFM .
17
5
⁄
16
"
24
1
⁄
2
"
27
9
⁄
16
"
TYP
27
5
⁄
8
"
29
11
⁄
16
"
TYP
30
13
⁄
16
"
32
5
⁄
8
"
TYP
33
1
⁄
4
"
TYP
CONDENSA TE
DRAIN TRAP
LOCA TION
(AL TERNA TE
UPFL OW )
7
⁄
8
-IN . DI A (22mm)
A CCESSOR Y
PO WER ENT RY
7
⁄
8
-IN . DI A (22mm)
PO WER CONN
CONDENSA TE DRAI N
TRAP LOCA TION
(DO WNFLO W &
HORIZONT AL LEFT )
26
15
⁄
16
"
24
1
⁄
2
"
22
5
⁄
16
"
2-IN . (51 mm) COMBUSTION-
AIR CONN
1
⁄
2
-IN . (13mm) DI A
GAS CONN
2-IN (51mm)
.
VENT CONN
1
⁄
2
-IN . DIA (13mm)
THERMOST AT ENT RY
22
11
⁄
16
"
SIDE INLE T
23
1
⁄
4
"
TYP
SIDE INLE T
1
1
⁄
4
"
1
"
OUTLET
26
15
⁄
16
"
28
1
⁄
2
"
22
5
⁄
16
"
19
"
13
⁄
16
"
5
⁄
8
"
5
⁄
16
"
1
"
39
7
⁄
8
"
22
1
⁄
4
"
TYP
11
⁄
16
"
7
⁄
16
"
24
3
⁄
16
"
BO TT OM INLE T
18
1
⁄
4
"
22
11
⁄
16
"
2-IN . (51mm)
COMBUSTION-AIR CONN
1
⁄
2
-IN . DI A (13mm)
GAS CONN
7
⁄
8
-IN . DI A (22mm)
PO WER CONN
1
⁄
2
-IN . DI A (13 mm)
THERMOS TA T ENTR Y
2-IN . (51 mm)
VENT CONN
DIMPLE LOCA T ORS
FOR HORIZONT AL
HANGING
14
1
⁄
2
"
TYP
SIDE INLE T
9
7
⁄
16
"
TYP
26
15
⁄
16
"
TYP
CONDENSA TE
DRAIN LOCA TIO N
(UPFLO W)
30
1
⁄
2
"
9
⁄
16
"
TYP
CONDENSA TE
DRAIN LOCA TION
(UPFL OW )
E
INLE T
11
/
16
"
11
/
16
"
D
13
/
16
"
13
/
16
"
OUTLET
A
AIRFL OW
26
1
⁄
4
"
26
1
⁄
4
"
CONDENSA TE DRAI N
TRAP LOCA TION
(DO WNFL OW &
HORIZONT AL RIGHT)
OR AL TERNA TE
1
⁄
2
-IN . DIA GAS CONN
(684 mm)
(667 mm)
(622 mm)
(567 mm)
(368 mm)
(32 mm)
(25mm)
(591 mm)
(684 mm)
(240 mm)
(439 mm)
(622 mm)
(700 mm)
(702 mm)
(754 mm)
(783 mm)
(829 mm)
(845 mm)
(21 mm)
(17 mm)
(17 mm)
(21 mm)
(775 mm)
(464 mm)
(14 mm)
(614 mm)
(565 mm)
(576 mm)
(483 mm)
(567 mm)
(667 mm)
(684 mm)
(724 mm)
(21 mm)
(16 mm)
(16 mm)
(1013 mm)
(25 mm)
(11 mm)
(25 mm)
(576 mm)
A05124
Dimensions -- In. (mm)
UNIT SIZE
A
D
E
060---14 / 042060
17---1/2 / 445
15---7/8 / 403
16 / 406
080---14 / 042080
21 / 533
19---3/8 / 492
19---1/2 / 495
080---20 / 060080
21 / 533
19---3/8 / 492
19---1/2 / 495
100---20 / 060100
21 / 533
19---3/8 / 492
19---1/2 / 495
120---20 / 060120
24---1/2 / 622
22---7/8 / 581
23 / 584
X
A92505
Heat Exchangers
Control Center
A02286
Inducer Assembly
ACRDJ AIR
CONDITIONING
RELAY DISABLE
JUMPER
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
CONNECTOR
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
MODEL PLUG
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
PL3 ECM BLOWER
HARNESS
CONNECTOR
PL1 LOW VOLTAGE MAIN
HARNESS CONNECTOR
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
PL2 HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
24-V THERMOSTAT
TERMINALS
DATE CODE XXXXN
FACTORY TEST
A09679
A06450
355B
A
V
4
PHYSICAL DATA
DESCRIPTION
UNIT SIZE
042060
042080
060080
060100
060120
Direct---Drive Motor Hp (ECM)
1/2
1/2
1
1
1
Motor Full Load Amps
7.7
7.7
12.8
12.8
12.8
RPM (Nominal)—Speeds
Variable 250 — 1300
Blower Wheel Diameter X Width (in.)
10 X 7
11 X 10
11 X 10
11 X 10
11 X 10
Filter Size (in.) Nominal A (Washable)
(1) 16 X 25 X 1 (1) 20 X 25 X 1 (1) 20 X 25 X 1 (1) 20 X 25 X 1 (1) 24 X 25 X 1
Shipping Weight (lb)
170
182
204
203
234
Limit Control
SPST
Heating Blower Control (Off Delay)
Selectable 90, 120, 150, or 180 SEC Intervals
Burners (Monoport)
3
4
4
5
6
Gas Connection Size
1/2---in. NPT
Gas Valve (Redundant) Manufacturer
Minimum Inlet Pressure (in. wc)
Maximum Inlet Pressure (in. wc)
White---Rodgers
4.5 (Natural Gas)
13.6 (Natural Gas)
Ignition Device
Hot Surface ---SiN
PERFORMANCE DATA
DESCRIPTION
UNIT SIZE
042060
042080
060080
060100
060120
Certified Temp Rise Range (
_
F)
Low
40—70
40—70
40—70
40—70
40—70
High
35—65
40—70
35—65
45—75
45—75
Certified Ext Static Pressure (ESP) (in. wc)
Heating
0.12
0.15
0.15
0.20
0.20
Cooling
0.50
0.50
0.50
0.50
0.50
Airflow CFM*
Heating Low
635 (700
{
)
860 (945
{
)
880 (970
{
)
1105 (1215
{
) 1325 (1455
{
)
Heating High
1070
1245
1490
1525
1900
Cooling (Max)
1400
1372
1975
1950
2060
Output Capacity Btuh
}
(ICS)
Low
37,000
50,000
50,000
63,000
75,000
High
56,000
75,000
75,000
94,000
113,000
AFUE%
}
95.0
95.0
95.0
95.0
95.0
Input Btuh**
Low
39,000
52,000
52,000
65,000
78,000
High
60,000
80,000
80,000
100,000
120,000
* Airflow shown is for bottom only return---air supply with factory---supplied 1---in. washable filter(s). For air delivery above 1800 CFM, see Air Delivery table for
other options.
{
Low heat CFM when low---heat rise adjustment switch (SW1---3) on furnace control is used.
}
AFUE and capacity in accordance with U.S. Government DOE test procedures.
** Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, reduce ratings 2% for each 1000 ft above sea level. In Canada, derate
the unit 5% for elevations from 2000 to 4500 ft above sea level.
355B
A
V
5
ELECTRICAL DATA
UNIT SIZE
042060
042080
060080
060100
060120
Unit Volts---Hertz---Phase
115---60---1
Operating Voltage Range (Min---Max)*
104---127
Maximum Unit Amps
8.9
8.9
13.8
13.8
13.8
Minimum Wire Size
14
14
12
12
12
Maxium Wire Length (ft)
{
31
31
32
32
32
Maximum Fuse or Ckt Brk (Amps)
}
15
15
20
20
20
Transformer (24v)
40va
External Control Power Available
Heating
25va
Cooling
34va
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
{
Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
}
Time---delay type is recommended.
BRYANT ACCESSORIES
DESCRIPTION
PART NO.
UNIT SIZE
042060
042080
060080
060100
060120
Vent Termination Kit (Bracket Only for 2 Pipes)
2---in. — KGAVT0101BRA
3---in. — KGAVT0201BRA
X
X
X
X
X
Concentric Termination Kit (Single Exit)
2---in. — KGAVT0701CVT
3---in. — KGAVT0801CVT
X
X
X
X
X
Condensate Freeze Protection Kit
KGAHT0101CFP
X
X
X
X
X
Germicidal Air Purifier
Model GAPA
X
X
X
X
X
Condensate Neutralizer Kit (obtained thru RCD)
P908---0001
X
X
X
X
X
Electronic Air Cleaner
Model EACA
X
X
X
X
X
Mechanical Air Cleaner
Model FILCAB or
EZXCAB
X
X
X
X
X
Humidifier
Model HUM
X
X
X
X
X
Heat Recovery Ventilator
Model HRV
X
X
X
X
X
Energy Recovery Ventilator
Model ERV
X
X
X
X
X
UV Lights
Model UVL
X
X
X
X
X
EZ Flex Media Filter with end caps --- 16---in. (9 pack)
EXPXXLMC0016
X
EZ Flex Media Filter with end caps --- 20---in. (9 pack)
EXPXXLMC0020
X
X
X
EZ Flex Media Filter with end caps --- 24---in. (6 pack)
EXPXXLMC0024
X
Replacement EZ Flex Filter --- 16---in. (10 pack)
EXPXXFIL0016
X
Replacement EZ Flex Filter --- 20---in. (10 pack)
EXPXXFIL0020
X
X
X
Replacement EZ Flex Filter --- 24---in. (10 pack)
EXPXXFIL0024
X
Exterior Filter Rack --- Universal, 1---in. (adjustable from 14---in. to
24---in.) with filter
KGAFR0301ALL
KGAFR0306ALL (6 pack)
X
X
X
X
Unframed Filter 1---in. — 16 x 25
KGAWF1301UFR
KGAWF1306UFR (6 pack)
X
S
S
S
Unframed Filter 1---in. — 20 x 25
KGAWF1401UFR
KGAWF1406UFR (6 pack)
X
X
X
Unframed Filter 1---in. — 24 x 25
KGAWF1501UFR
KGAWF1506UFR (6 pack)
X
355B
A
V
6
BRYANT ACCESSORIES (CONTINUED)
DESCRIPTION
PART NO.
UNIT SIZE
042060
042080
060080
060100
060120
Natural---To---Propane Gas Conversion Kit (Single Kit)*
KGANP4601ALL
X
X
X
X
X
Propane---To---Natural Gas Conversion Kit (Single Kit)
KGAPN3901ALL
X
X
X
X
X
ECM Motor Simulator (simulates the ECM blower and inducer
motor to aid troubleshooting)
KGASD0301FMS
X
X
X
X
X
Door Gasket Kit
KGBAC0110DGK
X
X
X
X
X
Advanced Product Monitor (software and hardware to link pc
laptop to control board)
KGAFP0301APM
X
X
X
X
X
ECM Control Replacement Module --- 1/2 HP
HK44EA123
X
X
ECM Control Replacement Module --- 1 HP
HK52EA123
X
X
X
Gas Orifice Kit Size 42 (Qty 50)
KGAHA0150N42
See Installation Instructions for model, altitude,
and heat value usages.
Gas Orifice Kit Size 43 (Qty 50)
KGAHA0250N43
Gas Orifice Kit Size 44 (Qty 50)
KGAHA0350N44
Gas Orifice Kit Size 45 (Qty 50)
KGAHA0450N45
Gas Orifice Kit Size 46 (Qty 50)
KGAHA0550N46
Gas Orifice Kit Size 47 (Qty 50)
KGAHA1550N47
Gas Orifice Kit Size 48 (Qty 50)
KGAHA850N48
Gas Orifice Kit Size 54 (Qty 50)
KGAHA0850P54
Gas Orifice Kit Size 55 (Qty 50)
KGAHA0750P55
Gas Orifice Kit Size 56 (Qty 50)
KGAHA0850P56
Gas Orifice Kit Size 1.25mm (Qty 50)
KGAHA05750125
Gas Orifice Kit Size 1.30mm (Qty 50)
KGAHA5750130
* Factory---authorized and field---installed. Gas conversion kits are CSA (AGA/CGA) recognized.
S --- 16 x 25 filters suitable for side return on all furnace sizes.
355B
A
V
7
THERMOSTAT AND ZONING CONTROL OPTIONS
NON---PROGRAMMABLE THERMOSTAT SELECTION
T6---NAC or T2---NAC
For use with 1 speed Air Conditioner ---
_
F/
_
C, Auto Changeover
T6---NHC or T2---NHC
For use with 1 speed Air Conditioner ---
_
F/
_
C, Auto Changeover
T2---NRH*
For use with 2 speed Air Conditioner ---
_
F/
_
C, Auto Changeover
* Model HP & 2 Stage thermostat must be field converted to air conditioner operation.
PROGRAMMABLE THERMOSTAT SELECTION
T2---PAC
For use with 1 speed Air Conditioner ---
_
F/
_
C, Auto Changeover, 7---Day
Programmable
T2---PHP*
For use with 1 speed Heat Pump ---
_
F/
_
C, Auto Changeover, 7---Day
Programmable
T2---PRH*
For use with 2 speed Air Conditioner ---
_
F/
_
C, Auto Changeover, 7---Day
Programmable
T2---PAC
For use with 1 speed Air Conditioner ---
_
F/
_
C, Auto Changeover, 5---2
Programmable
T2---PRH
{
For use with two---stage applications ---
_
F/
_
C, Auto Changeover, 7---Day
Programmable
T2---PRH
}
For multi---use/stage configurations ---
_
F/
_
C, Auto Changeover 7---Day
Programmable
* Model HP & 2 Stage thermostat must be field converted to air conditioner operation.
{
Hybrid Heat Dual Fuel system thermostat is used with furnace and heat pump application.
}
Thermidistat can be configured multiple use and staging. It must be configured for each specific application.
ZONING CONTROL SELECTION
ZONEBB3Z(AC/HP)01
Comfort Series Three---Zone Zone Kit
ZONEBB2KIT01---B
2---Performance Series Zoning/Temperature and Humidity Control
ZONEBB4KIT01---B
4---Performance Series Zoning/Temperature and Humidity Control
ZONEBB8KIT01---B
8---Performance Series Zoning/Temperature and Humidity Control
355B
A
V
8
AIR DELIVERY -- CFM (BOTTOM RETURN WITH FILTER)*
Unit Size
Operating Mode
CFM Airflow
Setting
External Static
Pressure Range*
External Static Pressure (ESP) In. W.C.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
042060
††
Low Heat
635†
0---0.50
635
635
625
615
615
High Heat
1070†
0---1.0
1070 1070 1070 1070 1070 1070 1070 1070 1065 1045
††
1---1/2---Ton A/C Cooling
525
0---0.50‡
525
525
510
495
465
††
2---Ton A/C Cooling
700
0---0.50‡
700
700
695
680
680
2---1/2---Ton A/C Cooling
875
0---1.0‡
850
870
875
875
870
860
845
825
810
805
3---Ton A/C Cooling
1050
0---1.0
1050 1050 1050 1050 1050 1050 1050 1050 1050 1045
3---1/2---Ton A/C Cooling
1225
0---1.0
1225 1225 1225 1225 1225 1225 1225 1225 1225 1205
Maximum
1400
0---1.0
1400 1400 1400 1400 1400 1400 1400 1400 1380 1325
042080***
††
Low Heat
900†
0---0.50
860
870
880
885
885
880
870
855
850
845
High Heat
1245†
0---1.0
1245 1245 1245 1245 1245 1245 1245 1235 1190 1145
††
1---1/2---Ton A/C Cooling
525
0---0.50‡
515
495
490
475
465
††
2---Ton A/C Cooling
700
0---0.50‡
685
680
670
665
665
2---1/2---Ton A/C Cooling
875
0---1.0‡
830
840
850
860
860
855
840
830
825
820
3---Ton A/C Cooling
1050
0---1.0‡
1050 1050 1050 1050 1050 1045 1040 1025 1015 1000
3---1/2---Ton A/C Cooling
1225
0---1.0‡
1225 1225 1225 1225 1225 1225 1225 1225 1185 1140
Maximum
1400
0---1.0‡
1400 1400 1400 1400 1375 1325 1280 1235 1190 1145
060080***
††
Low Heat
880†
0---0.50
880
880
880
875
880
High Heat
1500†
0---1.0
1485 1495 1500 1500 1500 1500 1500 1485 1475 1465
††
2---Ton A/C Cooling
700
0---0.50‡
670
640
635
630
630
††
2---1/2---Ton A/C Cooling
875
0---0.50‡
870
875
865
865
865
3---Ton A/C Cooling
1050
0---1.0‡
1050 1045 1040 1045 1045 1050 1050 1050 1045 1040
3---1/2---Ton A/C Cooling
1225
0---1.0‡
1225 1225 1225 1225 1225 1225 1225 1225 1225 1225
4---Ton A/C Cooling
1400
0---1.0‡
1330 1345 1360 1375 1380 1380 1380 1370 1365 1355
5---Ton A/C Cooling
1750
0---1.0
1750 1750 1750 1750 1750 1750 1745 1725 1700 1685
Maximum
2000
0---1.0
2000 2000 2000 2000 1975 1955 1920 1870 1820 1770
060100***
††
Low Heat
1110†
0---0.50
1105 1110 1110 1110 1110 1110 1110 1110 1110 1110
High Heat
1525†
0---1.0
1525 1525 1525 1525 1525 1525 1525 1510 1495 1470
††
2---Ton A/C Cooling
700
0---0.50‡
700
690
690
690
690
††
2---1/2---Ton A/C Cooling
875
0---0.50‡
835
845
855
860
865
3---Ton A/C Cooling
1050
0---1.0‡
1050 1050 1050 1050 1050 1050 1050 1050 1050 1050
3---1/2---Ton A/C Cooling
1225
0---1.0‡
1170 1190 1205 1220 1225 1225 1225 1225 1225 1225
4---Ton A/C Cooling
1400
0---1.0‡
1400 1400 1400 1400 1400 1400 1400 1400 1400 1375
5---Ton A/C Cooling
1750
0---1.0
1735 1740 1735 1735 1725 1720 1710 1695 1680 1660
Maximum
2000
0---1.0
1995 1985 1980 1965 1950 1935 1910 1885 1860 1815
060120
Low Heat
1330†
0---1.0
1325 1330 1330 1330 1330 1330 1330 1330 1330 1325
High Heat
1900†
0---1.0
1900 1900 1900 1900 1900 1885 1875 1860 1840 1815
††
2---Ton A/C Cooling
700
0---0.50‡
700
700
700
700
695
††
2---1/2---Ton A/C Cooling
875
0---0.50‡
870
875
875
865
870
3---Ton A/C Cooling
1050
0---1.0‡
1025 1035 1045 1050 1050 1050 1050 1050 1040 1025
3---1/2---Ton A/C Cooling
1225
0---1.0‡
1210 1210 1210 1225 1225 1225 1225 1225 1225 1225
4---Ton A/C Cooling
1400
0---1.0‡
1385 1400 1400 1400 1400 1400 1400 1395 1375 1370
5---Ton A/C Cooling
1750
0---1.0‡
1745 1730 1735 1735 1740 1735 1730 1725 1710 1685
6---Ton A/C Cooling
2100
0---1.0
2100 2100 2080 2065 2060 2045 2030 2000 1960 1895
Maximum
2100
0---1.0
2100 2100 2080 2065 2060 2045 2030 2000 1960 1895
* Actual external static pressure (ESP) can be determined by using the fan laws (CFM
2
proportional to ESP); such as, a system with 1750 CFM at 0.5 ESP
would operate at high---heating airflow of 1500 CFM at 0.37 ESP and low---heating airflow of 880 CFM at 0.13 ESP.
{
All heating CFMs are when low---heat rise adjustment switch (SW1---3) and comfort/efficiency adjustment switch (SW1---4) are OFF.
}
Ductwork must be sized for high---heating CFM within the operational range of ESP.
** Wattage data provided is for the circulating blower with bottom return and does not include draft inducer, accessories, or gas controls.
{{
Operation within the blank areas of the chart is not recommended because high---heat operation will be above 1.0 ESP.
*** All airflows on 21 in. casing size furnaces are 5% less on side return only installations.
355B
A
V
9
MAXIMUM ALLOWABLE PIPE LENGTH (FT / M)
Direct Vent (2---Pipe Only)
NUMBER OF 90
_
ELBOWS
UNIT SIZE
(BTUH)
ALTITUDE
Termination
Type
Pipe Dia
(IN.)*
1
2
3
4
5
6
60,000
0 to 2000
2 Pipe or 2---In.
Concentric
1---1/2
50 / 15.2
45 / 13.7
40 / 12.9
35 / 10.7
30 / 9.1
25 / 7.6
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
80,000
2 Pipe or 2---In.
Concentric
1---1/2
30 / 9.14
25 / 7.6
20 / 6.1
15 / 4.6
10 / 3.0
5 / 1.5
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
100,000
2 Pipe or 2---In.
Concentric
2
45 / 13.7
40 / 12.9
35 / 10.7
30 / 9.1
25 / 7.6
20 / 6.1
2---1/2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
120,000
2 Pipe or 3---In.
Concentric
2---1/2 one
disk
10 / 3.0
NA
NA
NA
NA
NA
3 one disk
35 / 10.7
30 / 9.1
15 / 4.8
NA
NA
NA
3 one disk†
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
UNIT SIZE
(BTUH)
ALTITUDE
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
60,000
2001 to
3000
2 Pipe or 2---In.
Concentric
1---1/2
45 / 13.7
40 / 12.9
35 / 10.7
30 / 9.14
25 / 7.6
20 / 6.1
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
80,000
2 Pipe or 2---In.
Concentric
1---1/2
26 / 7.9
21 / 6.4
16 / 4.9
11 / 3.4
6 / 1.8
NA
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
100,000
2 Pipe or 2---In.
Concentric
2
40 / 12.2
35 / 10.7
30 / 9.1
25 / 7.6
20 / 6.1
15 / 4.6
2---1/2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
120,000
2 Pipe or 3---In.
Concentric
3 one disk
31 / 9.4
26 / 7.9
12 / 3.7
NA
NA
NA
3 one disk†
63 / 19.2
62 / 18.9
62 / 18.9
61 / 18.6
61 / 18.6
61 / 18.6
UNIT SIZE
(BTUH)
ALTITUDE
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
60,000
3001 to
4000
2 Pipe or 2---In.
Concentric
1---1/2
42 / 12.8
37 / 11.2
32 / 9.8
27 / 8.2
22 / 6.7
17 / 5.2
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
80,000
2 Pipe or 2---In.
Concentric
1---1/2
25 / 7.6
20 / 6.1
15 / 4.6
10 / 3.0
5 / 1.5
NA
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
100,000
2 Pipe or 2---In.
Concentric
2
38 / 11.6
33 / 10.1
28 / 8.5
23 / 7.0
18 / 5.5
13 / 4.0
2---1/2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
120,000
2 Pipe or 3---In.
Concentric
3 one disk
29 / 8.8
24 / 7.3
10 / 3.0
NA
NA
NA
3 one disk†
59 / 18.0
59 / 18.0
58 / 17.8
57 / 17.4
57 / 17.4
56 / 17.0
UNIT SIZE
(BTUH)
ALTITUDE
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
60,000
4001 to
5000‡
2 Pipe or 2---In.
Concentric
1---1/2
40 / 12.2
35 / 10.7
30 / 9.1
25 / 7.6
20 / 6.1
15 / 9.6
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
80,000
2 Pipe or 2---In.
Concentric
1---1/2
23 / 7.0
18 / 5.5
13 / 4.0
8 / 2.4
NA
NA
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
68 / 20.7
100,000
2 Pipe or 2---In.
Concentric
2
36 / 11.0
31 / 9.4
26 / 7.9
21 / 6.4
16 / 4.8
11 / 3.4
2---1/2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
120,000
2 Pipe or 3---In.
Concentric
3 one disk†
56 / 17.1
55 / 16.8
54 / 16.5
53 / 6.2
52 / 15.8
52 / 15.8
UNIT SIZE
(BTUH)
ALTITUDE
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
60,000
5001 to
6000‡
2 Pipe or 2---In.
Concentric
1---1/2
37 / 11.3
32 / 9.8
27 / 8.2
22 / 6.7
17 / 5.2
12 / 3.7
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
80,000
2 Pipe or 2---In.
Concentric
1---1/2
22 / 6.7
17 / 5.2
12 / 3.7
7 / 2.1
NA
NA
2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
68 / 20.7
63 / 19.2
100,000
2 Pipe or 2---In.
Concentric
2
33 / 10
28 / 8.5
23 / 7.0
18 / 5.5
13 / 4.0
8 / 2.4
2---1/2
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
120,000
2 Pipe or 3---In.
Concentric
3 one disk†
53 / 16.2
52 / 15.8
50 / 15.2
49 / 14.9
48 / 14.6
47 / 14.3
*See notes on next page.
355B
A
V
10
MAXIMUM ALLOWABLE PIPE LENGTH (FT / M) (CONTINUED)
ALTITUDE
UNIT SIZE
(BTUH)
Direct Vent (2--Pipe Only)
NUMBER OF 90
_
ELBOWS
Termination
Type
Pipe Dia
(IN.)*
1
2
3
4
5
6
6001 to 7000‡
60,000
2 Pipe or 2---In.
Concentric
1---1/2
35 / 10.7
30 / 9.1
25 / 7.6
20 / 6.1
15 / 4.6
10 / 3.0
2
70 / 21.3
70 / 21.3
68 / 20.7
67 / 20.4
66 / 20.11
64 / 19.5
80,000
2 Pipe or 2---In.
Concentric
1---1/2
20 / 6.1
15 / 4.6
10 / 3.0
5 / 1.5
NA
NA
2
70 / 21.3
70 / 21.3
68 / 20.7
67 / 20.4
62 / 18.9
57 / 17.4
100,000
2 Pipe or 2---In.
Concentric
2
31 / 9.4
26 / 7.9
21 / 6.4
16 / 4.9
11 / 3.4
6 / 1.8
2---1/2
70 / 21.3
70 / 21.3
68 / 20.7
67 / 20.4
66 / 20.1
64 / 19.5
120,000
2 Pipe or 3---In.
Concentric
3 one disk†
49 / 14.9
48 / 14.6
47 / 14.3
45 / 13.7
44 / 13.4
43 / 13.1
ALTITUDE
UNIT SIZE
(BTUH)
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
7001 to 8000‡
60,000
2 Pipe or 2---In.
Concentric
1---1/2
32 / 9.8
27 / 8.2
22 / 6.7
17 / 5.2
12 / 3.7
7 / 2.1
2
66 /20.1
65 / 19.8
63 / 19.2
62 / 18.9
60 / 18.3
59 / 18.0
80,000
2 Pipe or 2---In.
Concentric
1---1/2
18 / 5.5
13 / 4.0
8 / 2.4
NA
NA
NA
2
66 / 20.1
65 / 19.8
63 / 19.2
62 / 18.9
57 / 17.4
52 / 15.8
100,000
2 Pipe or 2---In.
Concentric
2
29 / 8.8
24 / 7.3
19 / 5.8
14 / 4.3
9 / 2.7
NA
2---1/2
66 / 20.1
65 / 19.8
63 / 19.2
62 / 18.9
60 / 18.3
59 / 18
120,000
2 Pipe or 3---In.
Concentric
3 one disk†
46 / 14.0
44 / 13.4
43 / 13.1
41 / 12.5
40 / 12.2
38 / 11.6
ALTITUDE
UNIT SIZE
(BTUH)
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
8001 to 9000‡
60,000
2 Pipe or 2---In.
Concentric
1---1/2
30 / 9.1
25 / 7.6
20 / 6.1
15 / 4.6
10 / 3.0
5 / 1.5
2
62 / 18.9
60 / 17.8
58 / 17.7
56 / 17.1
55 / 16.8
53 / 16.2
80,000
2 Pipe or 2---In.
Concentric
1---1/2
17 / 5.2
12 / 3.1
7 / 2.1
NA
NA
NA
2
62 / 18.9
60 / 18.3
58 / 17.7
56 / 17.1
51 / 15.5
46 / 14.0
100,000
2 Pipe or 2---In.
Concentric
2
27 / 8.2
22 / 6.7
17 / 5.2
12 / 3.7
7 / 2.1
NA
2---1/2
62 / 18.9
60 / 18.3
58 / 17.7
56 / 17.1
55 / 16.8
53 / 16.2
120,000
2 Pipe or 3---In.
Concentric
3 one disk†
43 / 13.1
41 / 12.5
39 /11.9
37 / 11.3
35 / 10.7
34 / 10.4
ALTITUDE
UNIT SIZE
(BTUH)
Termination
Type
Pipe Dia
(IN.)*
NUMBER OF 90
_
ELBOWS
1
2
3
4
5
6
9001 to
10000‡
60,000
2 Pipe or 2---In.
Concentric
1---1/2
27 / 8.2
22 / 6.7
17 / 5.2
12 / 3.7
7 / 2.1
NA
2
57 / 17.4
55 / 16.8
53 / 16.2
51 / 15.5
49 / 14.9
47 / 14.3
80,000
2 Pipe or 2---In.
Concentric
1---1/2
15 / 4.6
10 / 3.0
5 / 1.5
NA
NA
NA
2
57 / 17.4
55 / 16.8
53 / 16.2
51 / 15.5
46 / 14.0
41 / 12.5
100,000
2 Pipe or 2---In.
Concentric
2
24 / 7.3
19 / 5.8
14 / 4.3
9 / 2.7
NA
NA
2---1/2
57 / 17.4
55 / 16.8
53 / 16.2
51 / 15.5
49 / 14.9
47 / 14.3
120,000
2 Pipe or 3---In.
Concentric
3 one disk†
39 / 11.9
37 / 11.3
35 / 10.7
33 / 10.1
31 / 9.5
29 / 8.8
* Disk usage---Unless otherwise stated, use perforated disk assembly (factory---supplied in loose parts bag).
{
Wide radius elbow.
}
Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA---Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion---air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter for both pipes.
3. Assume two 45
_
elbows equal one 90
_
elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
355B
A
V
11
MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT / M) WITH
INSULATION IN WINTER DESIGN TEMPERATURE AMBIENT*
UNIT SIZE
WINTER DESIGN
MAXIMUM PIPE DI-
INSULATION THICKNESS†
TEMPERATURE
AMETER (IN.)
0
3/8
1/2
3/4
1
042060
20
_
F / ---6.7
_
C
2
30 / 9.1
55 / 16.8
61 / 18.6
70 / 21.3
70 / 21.3
0
_
F / ---17.8
_
C
2
16 / 4.9
33 / 10.1
38 / 11.6
46 / 14.0
53 / 16.2
---20
_
F / ---28.9
_
C
2
9 / 2.7
23 / 7.0
26 / 7.9
33 / 10.1
38 / 11.6
042080
060080
20
_
F / ---6.7
_
C
2
37 / 11.2
65 / 19.8
70 / 21.4
70 / 21.3
70 / 21.3
0
_
F / ---17.8
_
C
2
20 / 6.1
39 / 11.9
45 / 13.7
55 / 16.8
63 / 19.2
---20
_
F / ---28.9
_
C
2
11 / 3.4
27 / 8.3
31 / 9.4
39 / 11.9
45 / 13.7
060100
20
_
F / ---6.7
_
C
2---1/2
41 / 12.5
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
0
_
F / ---17.8
_
C
2---1/2
21 / 6.4
42 / 12.8
48 / 14.6
59 / 18.0
68 / 20.7
---20
_
F / ---28.9
_
C
2---1/2
11 / 3.4
28 / 8.5
33 / 10.1
41 / 12.5
49 / 14.9
060120
20
_
F / ---6.7
_
C
3
49 / 14.9
70 / 21.3
70 / 21.3
70 / 21.3
70 / 21.3
0
_
F / ---17.8
_
C
3
26 / 7.9
51 / 15.5
58 / 17.7
70 / 21.3
70 /21.3
---20
_
F / ---28.9
_
C
3
15 / 4.6
35 / 10.7
40 / 12.2
50 / 15.2
59 / 18.0
* Pipe length (ft/m) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable
pipe length as specified in Table.
†
Insulation thickness based on R value of 3.5 per in.
CONCENTRIC VENT (DIRECT VENT/2--PIPE ONLY) (ALL MODEL SIZES)
C IN. DIA
B IN. DIA PVC
VENT/EXHAUST
1
3
/
16
B IN. DIA PVC
INTAKE/COMBUSTION AIR
D
E
F
A
1
1/2
A97110
Dimensions (in.)
KIT PART NO.
A*
B
C
D
{
E
F
KGAVT0701CVT
33---3/8
2
3---1/2
16---5/8
6---1/4
5---3/4
KGAVT0801CVT
38---7/8
3
4---1/2
21---1/8
7---3/8
6---1/2
* Dimension A will change proportionally as dimension D is lengthened or shortened.
{
Dimension D may be lengthened to 60 in. maximum. Dimension D may also be shortened by cutting the pipes provided in the kit to 12 in. minimum.
355B
A
V
12
CONDENSATE TRAP
CONDENSATE
TRAP (INSIDE)
BLOWER SHELF
ALTERNATE DRAIN
TUBE LOCATION
UPFLOW APPLICATIONS
CONDENSATE TRAP
DRAIN TUBE LOCATION
A06519
TYPICAL WIRING SCHEMATIC
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
JUNCTION
BOX
CONTROL
BOX
24-VOLT
TERMINAL
BLOCK
THREE-WIRE
HEATING-
ONLY
FIVE
WIRE
NOTE 2
NOTE 1
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
CONDENSING
UNIT
FURNACE
COM
R
W
C
Y
R
G
GND
GND
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
208/230- OR
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
WHT
BLK
WHT
BLK
A95236
W/W1
W2
Y/Y2
G
NOTES:
1.
2.
3.
A95236
355B
A
V
13
CLEARANCE TO COMBUSTIBLES
(LIT. TOP)
A09681
TYPICAL INSTALLATIONS
COMBUSTION AIR PIPE
A/C COIL
OUTDOOR UNIT
VENT PIPE
HUMIDIFIER
GAS-FIRED
WATER HEATER
ELECTRONIC
AIR CLEANER
AIRFLOW
FRONT OF
FURNACE
A06511
355B
A
V
14
GUIDE SPECIFICATIONS
General
System Description
Furnish a ______________________ (upflow) gas--fired
condensing furnace for use with natural gas or propane (factory--
authorized conversion kit required for propane); furnish cold air
return plenum; furnish external media cabinet for use with
accessory media filter or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI
Z 21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue Star
R
and Blue Flame
R
labels.
Unit efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest GAMA Consumer’s Directory of Certified Efficiency
Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon
request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed ball bearings, of _______hp,
and have infinitely variable speed from 300--1300 RPM
operating only when 24--VAC motor inputs are provided. Blower
motor shall be direct drive and soft mounted to the blower scroll
to reduce vibration transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(X) ________ in. An accessory highly efficient Media Filter is
available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted
galvanized steel.
Preferred
t
Plus 95i
Two--Stage/Variable Speed Gas Furnace
355BAV
ECM Inducer Motor
ECM Inducer motor shall be variable speed design, soft mounted
to assembly to reduce vibration transmission.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass 20 gauge corrosion--
resistant aluminized steel of fold--and--crimp sectional design and
applied operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a flow--through design
having a patented interior laminate coating of polypropylene for
greater corrosion resistance with fold--and--crimp design and
applied operating under negative pressure.
Controls
Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control,
a self--test feature that checks all major functions of the furnace,
and a replaceable automotive--type circuit protection fuse.
Multiple operational settings available, including separate blower
speeds for low heat, high heat, low cooling, high cooling and
continuous fan. Continuous fan speed may be adjusted from the
thermostat. Cooling airflow will be selectable between 350 or 400
CFM per ton of air conditioning. Features will also include
temporary reduced airflow in the cooling mode for improved
dehumidification when a Thermidistat is selected as the
thermostat.
Operating Characteristics
Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be 95% AFUE.
Air delivery shall be ________________ cfm minimum at 0.50
in. wc. external static pressure.
Dimensions shall be: depth_________in.; width __________in.;
height___________in. (casing only). Height shall be
_________in. with A/C coil and _________________in. overall
with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase
(nominal). Minimum wire size shall be ________AWG;
maximum fuse size of HACR--type designated circuit breaker
shall be _________ amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.