Full Text Searchable PDF User Manual
AQUASNAP JUNIOR
30RA / 30RH
INSTALLATION MANUAL
•
LL
O
Y
D
'S
R
E
G
IS
TE
R QUALIT
Y
A
S
S
U
R
A
N
C
E
I S O 900 1
30RA/30RH Puron
Water chillers, air-cooled with integrated hydronic section
GB - 1
ENGLISH
Table I
For operation and maintenance instructions of this unit as well as installation
instructions of the indoor unit, refer to the relevant manuals.
Contents
Pagina
Dimensions and weight .................................................................................................................
2
Technical data ................................................................................................................................
2
Minimum clearances ......................................................................................................................
3
Electrical data ................................................................................................................................
3
Data ...............................................................................................................................................
4
General information .......................................................................................................................
5
Warnings: avoid .............................................................................................................................
6
Water connections .........................................................................................................................
7
Connections and water circuits .....................................................................................................
8/9
Electrical connections ....................................................................................................................
10/12
Water-refrigerant heat exchanger .................................................................................................
12/13
Check the refrigerant charge .........................................................................................................
14
Unit maintenance ...........................................................................................................................
14
Control and safety devices ............................................................................................................
14
Diagnostics ....................................................................................................................................
15
Troubleshooting and guide for the owner ......................................................................................
16
Accessories ...................................................................................................................................
16
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A REFRIGERANT
• R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in colour.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of the cylinder in upright
position.
• The R-410A units must be charged with refrigerant in a liquid state. Use a commercial type metering
device in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
• R-410A, as other HFCs, is only compatible with the following oils selected by the compressor
manufacturer.
• The vacuum pump is not sufficient to remove moisture from the oil.
• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Never open unit to atmosphere while it is under a vacuum.
• When unit must be opened for service, break vacuum with dry nitrogen and replace filter dryer.
• Do not vent R-410A into the atmosphere.
Cooling only models
Heat pump models
Power supply
30RA005---7
30RH005---7
230 V ~ 50 Hz
30RA007---7
30RH007---7
230 V ~ 50 Hz
30RA007---9
30RH007---9
400 V 3N~ 50 Hz
30RA009---9
30RH009---9
400 V 3N~ 50 Hz
30RA011---7
30RH011---7
230 V ~ 50 Hz
30RA011---9
30RH011---9
400 V 3N~ 50 Hz
30RA013---9
30RH013---9
400 V 3N~ 50 Hz
Unit size
Oil type
Quantity
Drier already installed on
l
liquid line of the unit
005 - 007
POE
1.12
YES
009 - 011
POE
1.25
YES
013
POE
1.95
YES
30RA/30RH Puron
GB - 2
Unit capacities and power input (compressor and conventional pump watts) are based on:
cooling: outdoor air temperature 35
°
C d.b.; 24
°
C w.b., / water temperature - leaving 7
°
C / entering 12
°
C Eurovent 6/C/003-1998, CEN/TC113/WG5 N 4
heating: outdoor air temperature 7
°
C d.b.; 6
°
C w.b., / entering water temperature 40
°
C, leaving water temperature 45
°
C Eurovent 6/C/003-1998
Unit
30RA
30RH
005
007
009
011
013
005
007
009
011
013
Power input
Cooling
kW
2,07
2,70
3,05
3,22
4,57
2,02
2,57
2,95
3,28
4,56
Heating
kW
—
—
—
—
—
2,24
2,93
3,4
3,72
5,03
Compressor type
SCROLL
Water circulating pump selectable speeds
No.
3
3
3
3
3
3
3
3
3
3
Propeller fan motor - diameter
No./mm
1/370
1/370
1/370
2/370
2/370
1/370
1/370
1/370
2/370
2/370
Speed
rpm
840
1090
1030
1030
1030
890
1050
1200
1050
1200
Heat exchanger
WELDED PLATES
Water content
l
0,66
0,85
0,94
1,22
1,50
0,66
0,85
0,94
1,22
1,50
Expansion tank capacity
l
1
1
2
2
2
1
2
3
3
3
Nitrogen charge pressure
kPa
350
350
350
350
350
350
350
350
350
350
Expansion device
#
0,043
0,052
0,058
0,061
0,065
0,046/0,042 0,055/0,046 0,054/0,047 0,062/0,055 0,065/0,060
Table II: Technical data
Dimensions and weight
Mod. 30RA 005-007
Mod. 30RA 009
30RH 005-007-009
Mod. 30RA 011-013
30RH 011-013
Mod.
30RA
30RH
005
007
009
011
013
005
007
009
011
013
A
mm
800
800
800
800
800
800
800
800
800
800
B
mm
590
590
803
1264
1264
803
803
803
1264
1264
C
mm
300
300
300
300
300
300
300
300
300
300
D
mm
508
508
508
508
508
508
508
508
508
508
E
mm
146
146
146
146
146
146
146
146
146
146
F
mm
330
330
330
330
330
330
330
330
330
330
G
mm
97
97
97
97
97
97
97
97
97
97
H
mm
157
157
157
157
157
157
157
157
157
157
kg
kg
71
73
85
108
118
83
85
88
112
123
E
E
D
B
C
F
A
E
E
D
B
C
F
A
E
E
D
B
C
F
A
G
H
G
H
G
H
*
*
*
*
Electrical cables inlet
GB - 3
30RA/30RH Puron
E N G L I S H
Minimum clearances
F
A
B
A
C
D
E
F
D
E
Unit
30RA
30RH
005
007
007
009
011
011
013
005
007
007
009
011
011
013
Power supply
V - ph - Hz 230-1-50 230-1-50 400-3-50 400-3-50 230-1-50 400-3-50 400-3-50 230-1-50 230-1-50 400-3-50 400-3-50 230-1-50 400-3-50 400-3-50
Maximum power input*
kW
2,9
3,8
3,6
4,3
4,3
4,4
6,3
2,85
4
3,9
4,3
5,18
4,9
6,73
Locked rotor amps
LRA
58
82
35
40
97
48
64
58
82
35
40
97
48
64
Full load amps
FLA
11
13,5
5
6
17,5
8
9
11
13,5
5,5
6
17,5
8
9
Delayed fuses (class gL)
A
20
25
10
10
30
12
16
20
25
10
10
30
12
16
power supply protection
Section of the power
mm
2
3 x 2,5
3 x 2,5
5 x 2,5
5 x 2,5
3 x 4,0
5 x 2,5
5 x 2,5
3 x 2,5
3 x 2,5
5 x 2,5
5 x 2,5
3 x 4,0
5 x 2,5
5 x 2,5
supply conductors
Delayed fuses (class gL)
A
4
4
4
4
4
4
4
4
4
4
4
4
4
4
auxiliary circuit protection
Compressor
Capacitor
µ
F/V 40/450
50/450
-
-
60/450
-
-
40/450
50/450
-
-
60/450
-
-
Water circulating pump (230-1-50)
Current input
A
0,3
0,3
0,3
0,5
0,9
0,9
0,97
0,3
0,5
0,5
0,5
0,9
0,9
0,97
Capacitor
µ
F/V
3/400
3/400
3/400
4/400
7/400
7/400
7/400
3/400
4/400
4/400
4/400
7/400
7/400
7/400
Fan motor (230-1-50)
Current input
A
0,5
0,94
0,94
0,9
1,8
1,8
1,8
0,5
0,94
0,94
0,9
1,8
1,8
1,8
Capacitor
µ
F/V 2,5/450
4/450
4/450
4/450
4/450
4/450
4/450
2,5/450
4/450
4/450
3/450
4/450
4/450
3/450
Compressor crankcase
heater (230-1-50)
W
25
25
25
25
25
25
25
25
25
25
25
25
25
25
Current input
A
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
0,11
Note:
The main supply connecting cable must be H07 RN-F (or higher) type, synthetic rubber insulation with Neoprene coating, according to EN 60335-1 and
HD277.S1 codes.
Interlocks with the pumps or other accessories have to be inserted as shown in the notes on the wiring diagram
* Maximum unit power input with maximum load and non-compliant supply voltage.
Table III: Electrical data
Mod.
30RA 005 - 007
30RA 009 - 011 - 013
30RH 005 - 007 - 009- 011 - 013
A
mm
100
100
B
mm
250
250
C
mm
500
500
D
mm
50
100
E
mm
470
670
F
mm
400
400
GB - 4
30RA/30RH Puron
Table VIII: Operating limits
Data
Table IV: Control and safety device settings
open
closed
Refrigerant circuit high pressure switch
kPa
4206
2996
Water circuit safety valve
kPa
300
---
Freeze-up protection
°
C
2.7
*
Compressor first start delay
sec
60
Compressor start delay (OFF-ON)
sec
90
Compressor anti-cycling protection (OFF-ON)
cycle/h
12
*
When the compressor start delay has elapsed, the unit automatically restarts, if the
leaving water temperature is above 2.7
°
C.
Unit
30 RA/RH
Mod.
005
007
009
011
013
Water flow
l/s Nominal
0.25
0.31
0.37
0.46
0.54
System water content
l
Min.
17
22
27
32
41
30RH Max.
30
45
65
65
65
30RA Max.
50
50
100
100
100
Maximum operating pressure
kPa
300
300
300
300
300
Charge pressure
before operation
kPa
120
120
120
120
120
Maximum height difference
allowed with water at 50
°
C
m
20
20
20
20
20
Note:
Minimum head pressure
The minimum inlet head pressure at maximum water flow and a water
temperature of 50
°
C should be 13 kPa (about 1.3 mWG).
This precaution prevents cavitation noise and damage to the bearings
due to low water flow and insufficient bearing lubrication.
Table V: Water flow / System water content
Diameter
outside
inside
litres / metre
inches
mm
3/8 Gas
12.7
0.13
1/2 Gas
16.3
0.21
3/4 Gas
21.7
0.37
1 Gas
27.4
0.59
Table VII: Water content steel piping
Diameter-mm
outside
inside
litres / metre
14
12
0.11
16
14
0.15
18
16
0.20
22
20
0.31
28
25
0.49
35
32
0.80
Table VI: Water content copper piping
Min
Max
Power supply :
230 - 1 - 50
V
198
264
400 - 3 - 50
V
342
462
* ATTENTION:
For outside temperatures below 0
°
C, mix the correct amount of antifreeze
with the water.
Operating range - cooling
Leaving water temperature
°
C
Outdoor air temperature
°
C
Operating range - heating
Leaving water temperature
°
C
Outdoor air temperature
°
C
Minimum water temperature at start-up 3
°
C
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
18
15
10
4
-15 -10 -7 -5 0 2 5 10 15 20 25
55
50
45
40
35
30
25
20
15
Maximum water temperature at start-up 35
°
C
Important note:
Use of the buffes tank is not obligatory.
It may be necessary to use it to reach the minimum volumes shown
in table V.
Refer to the following example for the buffes tank:
GB - 5
30RA/30RH Puron
E N G L I S H
Choosing the installation site
Positions to avoid:
• Exposed to direct sun.
• Too close to sources of heat radiation, vapour or flammable gas.
• Particularly dusty areas.
Recommendations:
• Choose a position protected from opposing winds.
• Choose a position sheltered from direct sun.
• Choose an area where air outlet and unit noise will not bother
your neighbours. We advise inserting anti-vibration supports.
• Choose a position that allows for the clearances required.
• Floor structure should be adequately strong to support unit weight
and minimize vibration transmission.
• Consider a position which will not obstruct passageways or doors.
Fix the unit with locally purchased bolts countersunk in the base to
prevent overturning in case of strong winds.
• For heat pump models, unit must be adequately raised above
the ground surface.
• To empty the condensate water to a drain while operating in
heating mode, use the drain connection underneath on the left of
the pan and use a vinyl pipe with a 16 mm internal diameter.
This must not be used at temperatures lower than 0
°
C.
• If the unit is installed in areas where heavy snowfalls may occur, it
is necessary to raise its level at least 200 mm above the usual
snow level or alternatively to use the outdoor unit bracket kit.
General information
Unit installation
R-410A unit operate at higher pressures than standard
R-22 units. Do not use R-22 service equipment or components
of units for R-410A equipment.
Read this instruction manual thoroughly before starting the
installation.
• This unit complies with low-voltage (EEC/73/23) and electro-
magnetic compatibility (EEC/89/336) directives.
• The installation must be carried out by a qualified installer.
• Follow all current national safety code requirements. In particular
ensure that a properly sized and connected ground wire is in
place.
• Check that voltage and frequency of the main power supply are
those required; the available power must be adequate to operate
any other possible appliances connected to the same line.
Also ensure that national safety code requirements have been
followed for the main supply circuit.
• After installation thoroughly test the system operation and explain
all chiller functions to the owner.
• Leave this manual with the owner for consultation during future
periodic maintenance.
• The chiller and its components must be periodically inspected to
check for loose, damaged or broken parts.
If these faults are found and not eliminated, the unit could cause
physical injury and damage to goods and property.
IMPORTANT:
During the unit installation first make the water connections
and then electrical connections. If unit is removed first
disconnect electrical cables, then water connections.
WARNING:
Disconnect the main power supply switch before servicing the
system or handling any internal parts of the unit.
• The manufacturer declines any liability for damage resulting from
modifications or errors in the electrical or water connections.
• Failure to observe the installation instructions or use of the unit
under conditions other than those indicated in Table VIII “Operating
limits”, will immediately void the unit warranty.
• Failure to observe electric safety codes may cause a fire hazard in
case of short circuits.
• Inspect equipment for damage due to improper transportation or
handling: file an immediate claim with the shipping company.
Do not install or use damaged units.
• In case of any malfunctioning turn the unit off, disconnect the
mains power supply and contact a qualified service engineer.
• This unit contains R-410A refrigerant, a substance that does not
deplet the ozone layer.
• All manufacturing and packaging materials used for your new
chiller are compatible with the environment and can be
recycled.
• Dispose of the packaging material in accordance with local
requirements.
• This unit contains refrigerant that must be disposed of in a proper
manner. When disposing of the unit after its operational life,
remove it carefully. The unit must then be delivered to an
appropriate disposal center or to the original equipment dealer.
• When lifting the unit, never use hooks inserted into the side
handles, always use special equipment (e.g. lifting devices,
trolleys, etc.).
• Carefully recover refrigerant within this unit before final disposal or
when servicing. Never vent refrigerant to atmosphere.
Use approved recovery equipment for R-410A refrigerant.
Do not use equipment for R-22 refrigerant.
508 mm
330 mm
4 Ø 8 mm pins.
Protrusion height from the support
surface max. 20 mm.
햲
햳
햴
햲
100 mm min.
햳
20 mm gradient.
햴
Gravel-filled trench
햵
햶
햵
Drain connection
햶
Vinyl pipe
Snow
30RA/30RH Puron
GB - 6
Predominant head winds.
Multiple unit installation with units facing each other.
Insulating the connecting pipes only partially, which will cause
dripping.
Dripping into passageways.
Any obstruction of the unit air outlet and intake or any obstacle
that is too close (see minimum clearances required).
Installation on grassy ground or soft surfaces (in these cases a
solid foundation must be included).
Excessive height difference or excessive distance between chiller
and fan coil units.
Unnecessary turns and bends in the connecting pipes.
Any slack in the electrical connections.
Warnings: avoid....
GB - 7
30RA/30RH Puron
E N G L I S H
Water connections
1
2
5
3
4
max 20 m
1
2
3
4
8
10
9
14
7
7
11
12
*
The automatic air vent must be located at the highest
point of the circuit.
1
Unit water inlet Ø 1” F Gas
2
Unit water outlet Ø 1” F Gas
3
Drain
4
Air purge
5
Drain safety valve Ø 1/2” F Gas
Difference in height between water chiller and highest system point
Water connections
Water circuit: recommended wiring
1.
Brazed plate heat
exchanger
2.
Closed expansion
tank
3.
Circulating pump
4.
Flow switch
7.
Temperature sensor
8.
Safety valve
9.
30RA/RH unit
10.
Leaving water
11.
Return water
12.
Filter 10 mesh/cm
2
14.
Water drain connection
(chiller)
Field supplied piping
Manual air vent
Automatic air
vent
*
Water drain /
circuit drain
Shut-off valve
Pressure gauge
30RA/30RH Puron
GB - 8
Connections and water circuits
70
60
50
40
30
20
10
0
0,25
0,28
0,31
0,33
0,36
0,39
0,42
0,44
RA/RH 009
●
▲
■
RA/RH 011
80
70
60
50
40
30
20
10
0
●
▲
■
0,20
0,25
0,30
0,35
0,40
0,45
0,50
0,55
0,60
0,65
Available static pressure
Water flow rate l/s
60
50
40
30
20
10
0
0,17
0,19
0,22
0,25
0,28
0,31
0,33
RA 007
●
▲
■
A
vailable static pressure
(kPa)
Water flow rate l/s
A
vailable static pressure
(kPa)
Water flow rate l/s
Water flow rate l/s
RA/RH 013
80
70
60
50
40
30
20
10
0
0,20
0,25
0,30
0,35
0,40
0,45
0,50
0,55
0,60
0,65
●
▲
■
Water flow rate l/s
60
50
40
30
20
10
0
0,17
0,19
0,22
0,25
0,28
0,31
0,33
RA/RH 005
●
▲
■
Correction factors for ethylene glycol
Ethylene glycol
10%
20%
30%
40%
Freezing
temperature
–4
°
C
–9
°
C
–15
°
C
–23
°
C
Capacity
0.996
0.991
0.983
0.974
Power input
0.990
0.978
0.964
1.008
Water flow rate
1.000
0.979
0.979
1.025
Pressure drop
1.003
1.010
1.020
1.033
Connections and water circuits
• The hydraulic circuit must be designed to ensure a steady water
flow through the evaporator at any time.
• The water pipes in the circuit must be well supported and firmly
fastened to ensure that they do not put a strain on the
connections to the unit.
• Water inlet and outlet are identified by a tag.
• Air purge and water drain are located at the inlet and outlet
connections and are closed by appropriate plugs.
• Pipes must have shut-off valves to permit emptying of the heat
exchanger without draining the whole system, as suggested in
the diagram.
Control of a boiler
With a PRO-Dialog configuration, the unit (if it is in heating mode)
can control the start-up of a boiler via the mother board output
signal (see Service Interface Manual).
If the boiler is operating, the unit water pump is stopped.
The boiler output is activated:
– in 30RA units, by selecting heating mode
– in 30RH units, by selecting heating mode with the unit in fault
condition or with the unit operating at very low outdoor
temperature (see Service Interface Manual).
Water circulating pump
A single-phase, three-speed water circulating pump, to be
selected at installation, is installed inside the unit.
The water circulating pump, can be fitted with a water system
resistor (pressure drop) as indicated in the diagrams, keeping
water flow at the correct values.
If the system pressure drop is higher then the pump available
head, water flow to the unit and unit performances are reduced.
To reduce to minimum system pressure drop it is necessary:
- to reduce number of bends;
- to avoid elbow bends;
- to reduce the system extension to a minimum;
- to use pipes of the correct diameter.
To avoid possible damage due to water freezing, it is
recommended to install the water refill system inside the building.
It is recommend:
• to fit a replaceable filter of at least 10 mesh/cm
2
in the water
inlet, especially with welded joint iron pipes.
Water changes or additions should be reduced, if possible, as
they contribute to oxidation and to calcium deposit formation.
If the unit is not used for a long period, rotor shaft seizure can
occur; the user should unblock the rotor:
• switch off the system;
• remove the rubber plug from the panel (NOT available in the
versions 30RA005 / 30RA005H / 30RA007 / 30RA007H /
30RA007-9 / 30RA007H9);
• unscrew the air purge cap on the pump;
• insert a screwdriver in the slot and turn the rotor shaft;
• reassemble the air purge cap;
• put the rubber plug back on the panel;
• switch on the system.
Legend:
■
III high speed
●
II
medium speed
▲
I
low speed
Water temperature 20
°
C
60
50
40
30
20
10
0
0,17
0,19
0,22
0,25
0,28
0,31
0,33
RH 007
●
▲
■
A
vailable static pressure
(kPa)
Water flow rate l/s
A
vailable static pressure
(kPa)
A
vailable static pressure
(kPa)
A
vailable static pressure
(kPa)
GB - 9
30RA/30RH Puron
E N G L I S H
Remove electric box cover.
Connect the wires to the terminals according to the wiring diagram
and firmly tighten.
• The characteristics of the available power supply must
correspond to the unit nameplate specifications.
• The voltage must be within the limits indicated in the technical
data table.
• The imbalance between voltage phases must always be less
than 2%.
• WARNING:
If the unit operates at a voltage outside the limits given in Table
VIII or with a phase imbalance above 2%, this constitutes
improper use and may affect the warranty.
If the phase imbalance is higher than 2%, contact the local
electricity board immediately.
• Electric wiring must be in accordance with data indicated in this
manual and the wiring diagram and conform to applicable local
and national regulations.
• Ensure that mains supply connection is made through a switch
that disconnects all poles, with contact gap of a least 3 mm.
• The mains supply connecting cable must be H07 RN-F (or
higher) type, synthetic rubber insulation with Neoprene coating,
according to EN 60335-1 and HD277.S1 codes.
IMPORTANT:
• Make earth connection prior to any other electrical
connections.
• Earthing is required by law.
The installer must earth the unit using the terminal marked
with the international earthing symbol.
• Before connecting the supply cable to the line, locate line
(L), lines (L1-L2-L3) and neutral N. Then make connections,
as indicated in the wiring diagram.
WARNING:
The supply line of three-phase units must be three-phase plus
neutral. Omission of the neutral N line could damage the single-
phase supplies.
• The wiring diagram for the electrical supply to remote controls/
interlocks is inside the unit, glued under the cover.
• See Table III for cables sizes and dimensions of the electrical
devices.
Power circuit supply
• The power circuit supply (three-phase plus neutral) must be
connected to the correct terminals (see wiring diagram).
• The auxiliary circuit supply is directly taken from one phase and
neutral and it is proteced by fuse "F".
• If the electrical supply cables L1 (R), L2 (S), L3 (T) are
connected in an incorrect sequence, the power supply is
interrupted after a few seconds by the control, which goes into
alarm status preventing the incorrect compressor rotation.
Note:
After connections have been completed, replace electric box
cover.
Electrical connections
Connections and water circuits
The control can pilot an external pump with a current input of up
to 8 Ampere.
It is recommended to disconnect the internal pump, replacing it
with a tube.
WARNING:
The minimum inlet pressure to the pump at maximum water flow
should be 13 kPa at the maximum supply water temperature
(50
°
C).
This precaution avoids cavitation noise and damage to the pump
bearings due to lack of water flow and poor lubrication of the
bearings.
Flow switch
The flow switch in the outlet line to the pump stops the
compressor operation in case of:
• pump failure;
• water circulation cut-off;
• presence of air un the system.
햲
Position for units size
005 - 007 - 009
햲
햳
햳
Position for units size
011 - 013
30RA/30RH Puron
GB - 10
Electrical connections - single-phase models
Terminal block legend, single-phase models
Earth.
L
Live power supply.
N
Neutral power supply.
S1
ON/OFF switch
S2
HEAT/COOL switch
S3
Dual SET-POINT switch (standard/economy)
NOTE:
The contact rating must be greater than > 20 mA @ 24 V ac.
Unit without accessory AQUASNAP JUNIOR remote control
G
L
N
0
24
1
2
5
6
7
8
S1
S3
G
L
N
0
24
1
2
5
6
7
8
S1
S2
S3
Unit with accessory AQUASNAP JUNIOR remote control
G
L
N
0
24
1
2
5
6
7
8
1
2
5
6
7
8
3
4
G
L
N
0
24
1
2
5
6
7
8
1
2
5
6
7
8
3
4
30RA
30RH
30RA
30RH
A
B
A
B
A
B
A
B
A
B
Unit electrical panel
Terminal blocks
Electronic board connectors
Power supply 230 V 1ph 50 Hz
쐂
AQUASNAP JUNIOR remote control
Main switch
Time-delay fuse or circuit breaker (see table III "Electrical data").
A
B
Unit electrical panel
Terminal blocks
Electronic board connectors
Power supply 230 V 1ph 50 Hz
쐂
AQUASNAP JUNIOR remote control
Main switch
Time-delay fuse or circuit breaker (see table III "Electrical data").
Unit electrical panel
Terminal blocks
Electronic board connectors
Power supply 230 V 1ph 50 Hz
Available for remote alarm
(3 A @ 24 V ac max.)
Main switch
Time-delay fuse or circuit breaker
(see table III "Electrical data").
A
B
Unit electrical panel
Terminal blocks
Electronic board connectors
Power supply 230 V 1ph 50 Hz
Available for remote alarm
(3 A @ 24 V ac max.)
Main switch
Time-delay fuse or circuit breaker
(see table III "Electrical data").
B
A
Terminal block legend
Earth.
L
Live power supply.
N
Neutral power supply
햲
Control board
L N
L N
FUSE
24V
24V
FUSE
8
7
6
5
1
2
3
4
햲
GB - 11
30RA/30RH Puron
E N G L I S H
G
L1 L2 L3
N
0
24
1
2
5
6
7
8
S1
S3
G
L1 L2 L3
N
0
24
1
2
5
6
7
8
S1
S2
S3
L1 L2 L3 N
FUSE
8
7
6
5
N
L1 L2 L3
24V
24V
FUSE
1
2
3
4
30RA
30RH
A
B
Electrical connections - three-phase models
Terminal block legend, three-phase models
Earth.
L
Live power supply.
L1
Live power supply.
L2
Live power supply.
L3
Live power supply.
N
Neutral power supply.
S1
ON/OFF switch
S2
HEAT/COOL switch
S3
Dual SET-POINT switch (standard/economy)
NOTE:
The contact rating must be greater than > 20 mA @ 24 V ac.
Unit without accessory AQUASNAP JUNIOR remote control
Unit electrical panel
Terminal blocks
Electronic board connectors
쐆
Power supply 400 V 3N~ 50 Hz
Available for remote alarm (3 A @ 24 V ac max.)
Main switch
Time-delay fuse or circuit breaker
(see table III "Electrical data").
B
A
Unit electrical panel
Terminal blocks
Electronic board connectors
쐆
Power supply 400 V 3N~ 50 Hz
Available for remote alarm (3 A @ 24 V ac max.)
Main switch
Time-delay fuse or circuit breaker
(see table III "Electrical data").
B
A
30RA/30RH Puron
GB - 12
G
L1 L2 L3
N
0
24
1
2
5
6
7
8
1
2
5
6
7
8
3
4
G
L1 L2 L3
N
0
24
1
2
5
6
7
8
1
2
5
6
7
8
3
4
30RA
30RH
A
B
A
B
Electrical connections - three-phase models
Unit with accessory AQUASNAP JUNIOR remote control
Terminal box legend, three-phase models
Earth.
L
Live power supply.
L1
Live power supply.
L2
Live power supply.
L3
Live power supply.
N
Neutral power supply.
Unit electrical panel
Terminal blocks
Electronic board connectors
쐆
Power supply 400 V 3N~ 50 Hz
쐂
AQUASNAP JUNIOR remote control
Main switch
Time-delay fuse or circuit breaker
(see table III "Electrical data").
B
A
Unit electrical panel
Terminal blocks
Electronic board connectors
쐆
Power supply 400 V 3N~ 50 Hz
쐂
AQUASNAP JUNIOR remote control
Main switch
Time-delay fuse or circuit breaker
(see table III "Electrical data").
Water - refrigerant heat exchanger
Evaporator
Condenser
Water inlet
Chilled water outlet
Water inlet
Hot water outlet
Gas
Refrigerant
• The unit includes a brazed plate water-refrigerant heat
exchanger.
In the 30RA model the heat exchanger operates as a refrigerant
expansion evaporator whereas in 30RH units it operates as an
evaporator in the summer cycle and as a water-cooled
refrigerant condenser in winter cycle.
• Check if characteristics of the water in the refrigerant circuit are
correct. If necessary, treat water as appropriate.
CAUTION: In winter water frost may damage the unit.
To avoid freeze-up of the water contained in the system, one of the
following precautions must be taken during the winter cycle:
• drain the water from the system, using the drains in the lower part
of the unit,
or
• add the correct percentage of glycol to the water circuit.
Liquid + Gas
Liquid
GB - 13
30RA/30RH Puron
E N G L I S H
Water-refrigerant heat exchanger
Flow diagram for cooling only units
1. High pressure transducer
2. High pressure switch
3. Low pressure transducer
4. Pressure service port
5. Accurater expansion device
6. Crankcase heater
7. Suction accumulator
8. Water inlet
9. Chilled water outlet
10. Hot water outlet
11. Reversing valve
Refrigerant R-410A
Gas
Liquid + Gas
Liquid
Flow diagram for heat pump units: cooling cycle
Flow diagram for heat pump units: heating cycle
GB - 14
30RA/30RH Puron
Check the refrigerant charge
• This check becomes necessary after any refrigerant leak or
after the refrigeration circuit has been switched off to replace a
component.
• The best method to correctly charge refrigerant is to completely
empty the refrigerant circuit using refrigerant recovery
equipment.
Then charge the exact quantity of refrigerant according to the
data shown on the unit nameplate. This can be done with
charging equipment of the “Dial-a-charge” type.
• To empty the refrigerant circuit, the refrigerant recovery
equipment has to be connected to the high pressure side and
low pressure side service ports simultaneously (1/2” UNF,
20 threads/inch).
• R-410A refrigerant cylinders contain a dip tube which allows
liquid refrigerant to flow from the cylinder in an upright position.
Charge R-410A units with cylinder in upright position and a
commercial-type metering device in the manifold hose in
order to vaporize the liquid refrigerant before it enters the
unit. Charge refrigerant into the suction line.
• The above method must be used for heat pump systems
operating in heating, as operating difficulty in the winter season
(iced outdoor coil) impedes stable operating conditions.
Hence the refrigerant charge must be checked.
In cooling only systems, or heat pumps operating in the cooling
mode, the refrigerant charge check can be carried out using the
superheating method; this is only possible, if the ambient
temperature is above 15
°
C.
Unit maintenance
1. Compressor winding protection
Automatic reset.
This is activated when the temperature of the winding or the the
compressor power input exceed the set limits.
2. Freeze-up protection
This protection device is controlled by the Pro-Dialog Junior
control using the water heat exchanger leaving temperature.
This safety device interrupts unit operation and shows an alarm
code on the display.
3. Cooling control setpoint
This parameter is regulated by the control and factory set to an
entering water temperature of 12
°
C.
The second set point default value is 14
°
C and it can be selected
via the Service Interface.
4. Heating control setpoint
This parameter is regulated by the control and factory set to an
entering water temperature of 40
°
C.
5. High pressure switch HIP
Installed on the supply piping, set to 42 bar, with manual
electric reset.
The following maintenance operations must be carried out by
qualified personnel.
Cleaning the coil
When necessary, proceed as follows for more careful cleaning of
the coil:
Switch the mains supply OFF.
Remove unit top cover by losening holding screws and lifting
the cover.
Carefully clean the coil with a vacuum cleaner.
Also clean the inside of the fan compartment with a vacuum
cleaner.
Replace the unit cover and tighten the screws.
After long shutdown periods and at commissioning:
Energize the system by putting the main switch to ON without
starting the unit.
(The control must be in the OFF position for at least 12 hours
before the initial start up).
Do not disconnect the main switch during the unit operating
season.
Control and safety devices
6. Low suction temperature protection
Automatic/manual reset (after 6 automatic cycles) based on the
pressure transducer signal installed on the compressor suction
lines.
7. High pressure protection
Automatic/manual reset (after 6 automatic cycles) based on the
pressure transducer signal installed on the compressor discharge
lines.
8. Water flow switch FS
Installed on the water outlet to the heat-exchanger, does not
permit compressor and pump operation if there is no water
flow.
9. Defrost cycle
This operates only if ice is present on the heat exchanger during
heat pump operation.
This function can be operated by the control.
10. Solid state head pressure controller
Changes the fan speed according to the condensing temperature.
Is controlled by the Pro-Dialog Junior control and permits unit
operation up to the specified temperature limits, optimising the
condensing temperature.
GB - 15
30RA/30RH Puron
E N G L I S H
1 + 1 + 1=3
1
31
Diagnostics
The electronic control on the machine continuously monitors its
operation. In the event of a malfunction, it activates a relay whose
contact generates a coded alarm signal sending ON/OFF signals
to the remote control and switching on the alarm LED
.
Some alarm conditions are automatically reset, others require the
intervention of the operator to search for the fault, remove its cause
and switch the unit back on.
Manual resetting of alarm conditions
Manual resetting of alarm conditions is performed using the
remote ON/OFF button by simply switching OFF and then ON again
or opening and closing S1 switch (see electrical connections page 11).
WARNING: manual resetting causes the definitive loss of the alarm
code; therefore, before a manual reset, check the code according to
the instruction reported and remove its cause.
N.B. Temporary power supply failure to a unit in an alarm condition
does not reset the unit.
Alarm codification
The alarm code generated by a failure, is shown to the operator one
time only, and the unit remains in alarm status. To have the alarm
code shown again, press the ECO button on the remote control.
The alarm codification is based on the binary two-digit code X1 and
X2, as follows:
the first figure X1 flashes at 1 second intervals until it reaches the number
corresponding to the first digit, after a pause of 2 seconds, second figure
X2 starts to flash, again with 1 second intervals until the number
corresponding to the second is reached (only for two-digit codes).
Alarm code 31 with persistent alarm condition
LED on for 1 second
LED off for 1 second
To have the alarm code shown again, press the ECO button on the
remote control.
By pressing the ON/OFF button, the unit is turned OFF and the
alarm code is shown again. To restart the unit, remove the alarm
cause and press the ON/OFF button again.
Alarm
Description
Control
Alarm reset
Probable cause
code
action
method
1
Compressor fault
Compressor stopped Manual
Compressor overheated
2
Leaving water temperature
Unit stopped
Automatic
Sensor out of range, probe wire interruption
probe fault
or sensor fault
3
Entering water temperature
Unit stopped
Automatic
Sensor out of range, probe wire interruption
probe fault
or sensor fault
4
Defrost probe fault
Unit stopped
Automatic
Sensor out of range, probe wire interruption
or sensor fault
5
Air temperature probe fault
Unit stopped
Automatic
Sensor out of range, probe wire interruption
or sensor fault
6
High pressure transducer fault
Unit stopped
Automatic
Transducer out of range, incorrect transducer voltage
transducer wire interrupted or transducer fault
11
Low pressure transducer fault
Unit stopped
Automatic
Transducer out of range, incorrect transducer voltage
transducer wire interrupted or transducer fault
Automatic if the
12
Additional CCN
Unit stopped
board is
Board defect
clock/board fault
recognised again
13
Low refrigerant pressure
Unit stopped
Automatic/
Lack of refrigerant in the circuit, blocked
in the circuit
Manual
refrigerant filter or low pressure transducer fault
14
High refrigerant pressure
Unit stopped
Manual
Fan fault, coil obstructed, high outdoor
in the circuit
air temperature
15
High pressure safety switch /
The safety pressure switch has not been reset after
reverse compressor rotation
Unit stopped
Manual
the last alarm, incorrect compressor connection
16
Plate exchanger
Unit stopped
Automatic/
Low water flow rate entering or leaving
anti-freeze protection
Manual
water probe fault
Repeated attainment of low
Low pressure transducer fault,
21
suction temperature in cooling
Unit stopped
Automatic
refrigerant filter blocked
(more than six times)
or lack of refrigerant in the circuit
22
Repeated attainment of high
High pressure transducer fault
pressure condition in cooling
Unit stopped
Automatic
high air temperature,
(more than six times)
high entering water temperature
23
Repeated attainment of high
Unit stopped
Automatic
Low water flow rate entering or leaving
discharge temperature in heating
water probe fault
24
Repeated attainment of low
Unit stopped
Automatic
Low pressure transducer fault, refrigerant filter
suction temperature in heating
blocked or lack of refrigerant in the circuit
25
Low entering water
Unit stopped
Automatic
Entering water temperature too low,
temperature in heating
entering or leaving water probe fault
26
Outdoor interblock fault
Unit stopped
Manual
Flowswitch tripped or fault, air in the water circuit
31
CCN emergency shut-down
Unit stopped
Automatic
Network control
32
Loss of communication with the The unit operates
Automatic
CCN bus wiring defect or
Flotronic or Chiller System Manager
in local mode
fault in the system
33
Maintenance service request
Unit stopped
Manual
–
The following list describes the possible cause for each alarm code:
GB - 16
30RA/30RH Puron
Troubleshooting, guide for the owner and accessories
Troubleshooting
Unit compressor and fan will not start:
• Unit not energized; check the mains power connections.
• Mains switch OFF; check and put in the ON position.
• Main switch fuses have blown; replace.
• Wait for 2 minutes; compressor cycling protection is on.
• Pressure switch open; check and eliminate cause.
• Mains voltage too low.
• Electrical connections loose or wrong; check and repair.
Compressor will not start, but unit fan is running:
• Electrical connections of compressor loose or wrong; check andrepair.
• Compressor burnt out, seized or protection device open; check for
the cause and replace compressor if necessary.
• Run capacitor faulty (single-phase models); replace.
Compressor starts, but stops due to its overtemperature
protection (other than stops caused by the normal operation
of the thermostat):
• Wrong refrigerant charge (excessive or low) or air or other non-
condensable gases in the circuit; drain refrigerant (see note 1),
evacuate and recharge.
• Mains voltage wrong (too high or too low).
• Condenser coil obstructed; remove obstructions.
• Fan off; check cause and repair.
• Run capacitor faulty; check and replace.
• Indoor unit thermostat faulty; replace.
• Refrigerant circuit clogged; check and remove obstructions.
• Reversing valve faulty in heat pump models; replace.
• Expansion device clogged or covered with ice; drain refrigerant
(see note 1), evacuate and recharge.
Compressor runs continuously:
• Unit selected too small for actual air conditioning needs.
• Water temperature selection too low (if in cooling) or too high (if in
heating, for heat pump models); check temperature selection.
• Refrigerant charge low; check and add refrigerant.
• Outdoor unit fan faulty; replace.
• Air or other non-condensable gases in the circuit; drain refrigerant
(see note 1), evacuate and recharge.
• Obstruction in the air intake or dirty indoor unit filters; remove
obstruction or clean filter.
Frequent ice build-up on coil (during heating with heat
pump units):
• Fan stopped; check cause and repair.
• Wrong electrical connections on defrost circuit; check electrical
connections and repair.
Discharge pressure too high:
• Coil dirty or obstructed; clean or remove obstructions.
• Water flow rate is insufficient or the pump is faulty (during
heating); replace.
• Refrigerant charge too high; drain some refrigerant (see note 1).
• Air or other non-condensable gases in the circuit; drain refrigerant
(see note 1), evacuate and recharge.
Discharge pressure too low:
• Refrigerant charge too low; add refrigerant.
• Coil dirty or obstructed; clean or remove obstructions.
• Water filter dirty; clean filter.
Suction pressure too high:
• Internal high pressure relief valve open; check for cause and repair.
• Refrigerant charge too high; drain some refrigerant (see note 1).
• Reversing valve (on heat pump models) faulty or internal leak;
replace.
Suction pressure too low:
• Refrigerant charge too low; add refrigerant.
• Evaporator coil (indoor or outdoor in case of heat pump models)
covered with ice; see the following points.
• Air circulation on the evaporator unit not sufficient; check for the
cause and repair.
• Expansion device or suction line clogged: check and repair.
• Fan does not stop during defrost periods (when heating with heat
pump models); check electrical connections.
• Defective defrost probe (heating with heat pump models); replace.
• Contact between tube and defrost probe (heating with heat pump
models) faulty; check and repair.
Fan cycling due to its overtemperature protection:
• Fan capacitor faulty; replace.
• Electrical connections loose; check connections.
• Fan bearing seized; check and repair.
• Expansion device clogged or covered with ice; drain refrigerant
(see note 1), evacuate and recharge.
Note 1:
Do not release refrigerant to the atmosphere; use
refrigerant recovery equipment.
Guide for the owner
When installation and tests are completed explain the Operation
and Maintenance Manual to the owner, with particular attention to
the main operating modes of the air conditioner, such as:
• Turning the unit on and off.
• Control functions.
In the event of a fault or malfunctioning, check the error code
shown on the remote control or at the LED on the board in the
chiller control panel.
NOTE
(1)
: Exclusively for service use
Table IX: Accessories
Description
Part number
Mod. 30 RA/RH
005
007
009
011
013
AQUASNAP JUNIOR remote controller
30RAJ9002
앬
앬
앬
앬
앬
Aquasmart control
CEAS430408-01SA
앬
앬
앬
앬
앬
Service interface
(1)
30RAJ9003
앬
앬
앬
앬
앬
Mechanical water filter
30RAJ9004
앬
앬
앬
앬
앬
CCN clock board
X30RA20J010
앬
앬
앬
앬
앬
L010126H39 - 0404
Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1
The manufacturer reserves the right to change any product specifications without notice.
April, 2004. Printed in Italy