GW1000

User’s Guide

Revision 1.04 – Mar 30, 2008

DataLink Technologies Gateways, Inc.

Website: www.datalink-networks.com

Tel : (604) 632-4278 / (866) 709-6390

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

2

Table of Contents

1.0 GW1000 General Operation & Applications

................................................................. 3

2.0 Hardware Specifications

................................................................................................... 4

3.0 GW1000 Hardware Layout

................................................................................................ 5

4.0 Configuration

........................................................................................................................ 6

4.1 Online Mode of Operation

.......................................................................................................... 6

4.3 Restore Factory Defaults

.......................................................................................................... 10

4.4 USB Driver Installation

.............................................................................................................. 12

4.5 Firmware Upgrade

...................................................................................................................... 12

5.0 Switch and LED Indicator Functions

........................................................................... 16

6.0 GW1000 Wiring Diagrams

............................................................................................... 18

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

3

1.0 GW1000 General Operation & Applications

The GW1000 continues the functionality of the current DL2000/DL3000/DL3500
product line.  In addition to having connectivity to Allen-Bradley’s DH+, and the
RS232/422/485/USB capabilities of the DL3500, the GW1000 offers a 10/100 Base-T
Ethernet connection.  The ability to power the GW1000 from the USB communication
link is also present, removing the sometimes cumbersome procedure of locating a DC
power supply when using laptops or PC’s in the field.

The GW1000 has two communication ports.  Channel A is designed to connect to your
industrial Allen-Bradley DH+ network.  Channel B is used to connect to your serial or
USB device, the protocol depends on which model of the GW1000 you have ordered. 
Channel B has the capabilities of RS232C, RS422, RS485 and USB 2.0.

Configuration of the operating parameters is done quickly and easily via the Ethernet
interface.  Operational Firmware is also easily upgraded over the Ethernet interface. 
This allows for quick changes if you need to change your protocol.

Currently there are three standard GW1000 products available to allow access to Allen-
Bradley’s DH+ network.  Many other custom ASCII and serial protocols have been
implemented to DH+ on the GW1000 platform. 

Contact DataLink Technologies to see if the GW1000 is the correct device for your
communication needs.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

4

2.0 Hardware Specifications

2.1 Operating Specifications:

  CHA can be configured DH+ with baud rates of 57.6, 115.2 and 230.4 KBaud

  CHB has full RS232C, as well as both RS422-4 wire and RS485 2-wire modes. 

CHB has the ability of being configured with asynchronous speeds up to 230.4
KBaud as well as the new Plug and Play Windows USB Interface.

  Currently DF1, Modbus, and ASCII are the supported protocols. Custom protocols

are easily implemented.  Both CRC 16 and BCC error checking can be
implemented; custom error checking can be added at the customer’s request.

  Simple Parameter Configuration using Ethernet interface.

  Configuration and Reset Pushbuttons to set up online configuration parameters and

perform a full Hardware Reset as well as a Restore to Factory Defaults option.

  Operating Parameters are stored in non-volatile flash memory.  The GW1000

firmware can be upgraded via the Ethernet interface.

  Bi-Color (Green/Red) LED’s for each communication channel indicates activity and

status.  Green POWER LED indicates power on.

2.2 Physical Specifications:

Dimensions: 0.90" H x 4.65" D x 3.98" W  (22.8mm x 118.3mm x 101.0mm)
Weight: 0.44lbs (0.2kg)
Installation: Plastic enclosure; Freestanding or DIN rail mounting with integrated clip
Operating Environment: 32 to 122 °F (0 to 50 °C)
Storage: -40 to 185°F (-40 to 85°C)
Humidity: 5% to 95% non-condensing
Power: 9-27V DC or standalone USB - 2.0 Watts

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

5

3.0 GW1000 Hardware Layout

   This Section contains information on the physical position and purpose of the
components of the GW1000.

Top side connectors

  3-pin power – 3.81mm pitch removable screw terminal plug

  3-pin A-B DH+ – 5.08mm pitch removable screw terminal plug

  RJ45 Ethernet

Bottom side connectors (note: one connection is permitted at a time)

  5-pin RS485/RS422 for CHB – 3.81mm pitch removable screw terminal plug

  9 Pin D9M connector for CHB RS232C communications

  USB connector for CHB

Front Panel Indicators

  DH+ Status

  Serial Status

  Serial Receive (RX)

  Serial Transmit (TX)

  Ethernet Activity

  Ethernet Link

  Power

RESET and CONFIGure pushbuttons are accessible through openings in the top of the
case as depicted on product label.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

6

4.0 Configuration

4.1 Online Mode of Operation

Online Mode is the normal operating Mode of the GW1000.  In this mode the Channels
are configured and the GW1000 is ready to interface to your equipment. 

Power on or a press of the Reset pushbutton automatically puts the GW1000 into
Online mode.

4.2 Configuring the GW1000

Connect the GW1000 ethernet port to a switch or hub on the same network as your PC
using a CAT5 network patch cord.  Power on the GW1000 and wait 30 seconds for the
bootup sequence to complete.  Note the LAN 

LINK

 indicator LED should be on.  From

Windows, open a DOS command prompt window by clicking:

START 

 All Programs 

 Accessories 

 

Command Prompt

At the command prompt, type:

telnet 192.168.1.111 10000   (ENTER

)

This will bring up the login screen for configuration. (note: if you have changed the
default IP address of the GW1000, enter the new address.  If you do not know the IP
address programmed into the GW1000, first restore factory defaults.)

Welcome to Gateway 1000 Interface Configuration Utility 1.0
Serial Number: A000800042

login:

Type in the default login and password as: “

Netsilicon

” and “

sysadm

” respectively. 

Please note the login is case-sensitive. 

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

7

The following is the main menu:

Hello Netsilicon

DataLink GW1000-DHP1:DF1 to DH+ Interface Main Menu.
Build : 0803.1.11
        1.) Modify IP Parameters
        2.) Modify Password
        3.) View/Modify Online Parameters
        4.) Online Diagnostic Statistics
        5.) Save and Reboot
        6.) Quit without save

Enter Selection:

To access a menu item, press the corresponding number followed by ENTER

1) Modify IP Parameters

To edit the IP Parameters, press “1” followed by ENTER

.  The following submenu is

displayed.

Enter Selection: 1

        IP Parameters:
        1.) IP Address          192.168.1.111
        2.) Subnet Mask         255.255.255.0
        3.) Default Gateway     192.168.1.1
        4.) Main Menu

To edit the IP address, press “1” ENTER

 f

ollowed by a new address and ENTER

.

Likewise, the Subnet Mask and Default Gateway can be set.

Enter Selection: 1
Enter IP address: 192.168.1.33
New IP address [192.168.1.33] accepted

        IP Parameters:
        1.) IP Address          192.168.1.111
        2.) Subnet Mask         255.255.255.0
        3.) Default Gateway     192.168.1.1
        4.) Main Menu

Enter Selection:

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

8

Note: The new parameters will be written to memory upon returning to the main
menu by pressing 4 ENTER

.

2) Modify Password

The login password can be modified with main menu option 2.

Enter Selection: 2

Enter old password: ******

Enter new password: ******

Renter new password: ******

New password accepted

3) View / Modify Online Parameters

To edit the Online Parameters for DH+ port and serial port, from the main menu, press
“3” followed by ENTER

.  The following submenu is displayed.

Enter Selection: 3

        Online Parameters:
        1.) Node Address                Oct:1o, Hex:0x01, Dec:1
        2.) DH+ Baud Rate               57.6 KBaud
        3.) Serial Parameters
        4.) DF1 Parameters
        5.) Save Parameters and Exit
        6.) Return to Main Menu

Enter Selection:

To edit the DH+ node address, press “1” ENTER

enter the two-digit octal value and

press ENTER

..

Enter Selection: 1

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

9

Enter new DH+ Node address (Octal):

To edit the DH+ baud rate, press “2” ENTER

 and 

select a value and press

ENTER

..

Enter Selection: 2

        DH+ Speed:      [57.6 KBaud]
        1.) 57.6K Baud
        2.) 115.2K Baud
        3.) 230.4K Baud
        4.) Autobaud Detection
        5.) or <CR> Keep as Configured and Return to Online
Parameters Menu

To edit the parameters for the serial port, press “3” ENTER

 and 

the following

submenu is displayed.  Each of the parameters can be changed with corresponding
submenus.  To save the serial settings,  press “7” ENTER

.

Enter Selection: 3

        Serial Parameters:
        1.) Baud Rate                   9600
        2.) Parity                      NONE
        3.) Data Bits                   8
        4.) Stop Bits                   1
        5.) Interface (RS232/422/485)   RS232
        6.) RS232 RTS/CTS Handshaking   NONE
        7.) Return to Online Parameters Menu

Enter Selection:

The following DF1 protocol parameters can be edited with option 4 and their associated
submenus.

Enter Selection: 4

        DF1 Protocol Parameters:
        1.) Error Checking Mode         BCC
        2.) Duplex Protocol             FULL
        3.) PASS/EXECUTE Diagnostics    PASS
        4.) Return to Online Parameters Menu

Enter Selection:

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

10

Note: To save the values and exit, press “5” from the Online Parameters menu:
“Save Parameters and Exit.”

4) Online Diagnostic Statistics

An online diagnostics menu is provided for troubleshooting purposes.

Enter Selection: 4

        Online Diagnostics Statistics and Counters
        1.) DH+ Diagnostic Counters
        2.) DF1 Diagnostic Counters
        3.) Return to Main Menu

Enter Selection:

4.3 Restore Factory Defaults

To restore factory defaults, connect the GW1000 to a PC using either a USB or RS232
connection.  If using USB, first install USB drivers as explained in “USB Driver
Installation”.  Using a terminal program such as “Hyperterminal” included with Microsoft
Windows, configure a connection to the RS232 port on the PC (typically COM1 or
COM2) or the virtual COM port assigned by the USB driver.  This setting is under File

 Properties menu.  Press “

Configure

” and select baud rate of 57.6 Kbaud, 8 data

bits, no Parity, 1 stop bit, flow control: none.

  Power on the GW1000 by connecting power supply or USB cable.

  Wait 30 seconds for the bootup sequence to complete

  In the Hyperterminal program, select  Call 

 Call to connect to the selected COM

port.

  Through the window in the side of the GW1000 case, press the “

Config

” button with

a paperclip or small screwdriver.  The config button should be pressed for one
second and then released.

  The following screen is displayed

PLATFORM: ns7520_a_esp
BSP Library Built on: Mar 30 2008 11:25:37
APPLICATION: DataLink GW1000-DHP1 : DF1 to DH+ Interface
Application Built on: Mar 30 2008 11:26:31
-----------------------------------------------------------------
NETWORK INTERFACE PARAMETERS:
  IP address on LAN is 192.168.1.111
  LAN interface's subnet mask is 255.255.255.0

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

11

  IP address of default gateway to other networks is 192.168.1.1
HARDWARE PARAMETERS:
  GW1000's serial number is A00800333
  GW1000's Ethernet MAC Address is 00:50:C2:89:F0:29
  After board is reset, start-up code will wait 5 seconds
  Default duplex setting for Ethernet connection: default
ONLINE DH+ PARAMETERS:
  Serial DF1/Config channel will use a baud rate of 57600
  DH+ Node address is 22 Octal.
  DH+ baud Rate is 57600 Baud.
  DF1 Parameters: Full Duplex Operation, and BCC Error Checking.
-----------------------------------------------------------------
Press any key in 5 seconds to change these settings.

  Press a key…

Press A to Accept the settings, or M to Modify?

  Press “

M

” followed by ENTER

 to modify settings…

Enter the root password:

  At the password prompt, type “

Netsilicon

”.  Note password is case-sensitive…

Reset configuration to default values [N]?

  Type “

Y

”, ENTER

 to restore settings to default values, then press ENTER

 at each

prompt to accept default values, or enter desired new values followed by ENTER

For each of the following questions, you can press <Return> to
select the value shown in braces, or you can enter a new value.

ETHERNET INTERFACE SETTINGS:

Obtain IP settings automatically using DHCP for this interface
[N]?
IP address  [192.168.1.111]?
Subnet mask  [255.255.255.0]?
Gateway address  [192.168.1.1]?

This interface must have a unique MAC address.
Ethernet MAC Address [00:40:9D:43:35:97]?
Ethernet duplex setting (default, full, half)? [default]

SERIAL CONSOLE PORT SETTINGS:

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

12

Set the baud rate of the serial console port [57600]?
    9600, 19200, 38400, 57600, 115200

SECURITY SETTINGS:

Would you like to update the Root Password [N]?
Would you like to update the Administrator 'admin' Password [N]?

MISCELLANEOUS SETTINGS:

Each development board must have a unique serial number
Set the board's serial number[A00800333]?

How long (in seconds) should CPU delay before starting up [5]?

Saving the changes in NV memory...

Default Settings

DF1 protocol:
9600 Baud, 8 Bits, No Parity, BCC Checksum

DH+ defaults
57.6  KBaud
Node address: 1 octal, 0x01 hex, decimal 1

4.4 USB Driver Installation

The USB driver is provided by Future Technology Devices International Ltd.  Please
see the Windows_XP_Installation_Guide.pdf in the Documentation folder on the CD
included with the GW1000.  The USB driver version on the CD is “CDM 2.02.04 WHQL
Certified.”  See section “2.1 Installing CDM drivers” on page 4.  For reference, the
document is also available here…

http://www.ftdichip.com/Documents/InstallGuides/Windows_XP_Installation_Guide.pdf

4.5 Firmware Upgrade

Firmware upgrade is accomplished using the ethernet interface and a web browser. 
Connect the GW1000 ethernet port to an ethernet port on the same network as your
PC using a CAT5 network patch cord to a network hub or router.  Open a web browser
such as Microsoft Internet Explorer or Mozilla Firefox, power on the GW1000 and wait
30 seconds for bootup sequence to complete.  Note the LAN 

LINK

 indicator LED

should be on.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

13

In the browser address bar, type 

192.168.1.111

 and press ENTER

.  (note: if you have

changed the default IP address of the GW1000, enter the new address in the address
bar.  If you do not know the IP address programmed into the GW1000, first restore
factory defaults.)  In the “User Name” field, type “

root

”.  In the Password field, type

Netsilicon

”.  (note: password is case-sensitive.)

Click 

OK

 and the home page will be displayed.  The current software version is

displayed in the lower right of the screen.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

14

Click “

Upload Firmware

Click 

Browse

 or type the location of the new firmware file.  (note: the firmware image

filename must 

not

 be edited.  The filename must be 

image.bin.  

If you have multiple

versions of firmware files, they must each be stored in a different folder on your
computer.)  Click 

Upload

.  Please wait two minutes until you see the “

Upload

Successful

” message.  On rare occurrences, the browser program may timeout before

a successful response is received.  In this case, wait an extra minute to make sure the
upload has taken place, repower the GW1000, and login as explained above.  Examine
the firmware release number in the lower right of the screen to check the version has
been updated.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

15

To finalize firmware update, you must cycle power on the GW1000.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

16

5.0 Switch and LED Indicator Functions

5.1 Switch Functions

The Reset pushbutton will perform a complete hardware reset of the GW1000.  It
is identical to a complete power cycle and will cause the GW1000 to go through
its LED start-up sequence.

The Configure pushbutton takes the GW1000 out of On-Line operation mode
and allows the user to restore factory default settings.

5.2 Indicator Functions

5.2.1 Power-Up and Reset Sequence

On Power-up or after the Reset button has been pressed the GW1000 executes
a self-diagnostic check of the RAM and flash firmware.  The correct LED
indicator sequence to show the GW1000 is functioning properly is as follows:
After all LEDS go out.

LED

STATUS

Power

Green Continuously

Serial Tx

Brief green flash then off

Serial Rx

Green for 3 seconds then off

Status 

Red for 10 seconds then Green 1 second, then off

DH+ 

Green 1 second, Red 1 second, then flashing green for offline,

solid green for online.

After this sequence the GW1000 goes into the On-line mode of Operation.  The
LED indicators will behave in the way defined by the GW1000 model used. 
Normally, all LEDS will be off waiting for communication on its channels.

5.2.2 Normal On-line Operation

The following is a description of the normal operation of the Channel LEDs on
the GW1000.  Custom products operation will differ from the following:

LED

Description of Operation

Power

Green Indicates Power is being supplied to the GW1000.

Serial Tx,

Flashes GREEN  when a Character is Received or

& Serial Rx

Transmitted.  If Characters are being received or transmitted

rapidly, the LED might appear on SOLID.

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

17

            Status 

Flashes RED for 0.5 seconds if a NAK is received or transmitted in
DF1 protocol or if all serial communication buffers are full.
Flashes GREEN for 0.5 seconds if Good DF1 packets are being
sent.  If Characters are being received or transmitted rapidly, the
LED might appear on SOLID.

DH+

Flashes RED if a Duplicate DH+ node address is already on the

network.  Flashes GREEN when soliciting for stations to create a
new network or DH+ cable is not connected.  Alternately flashes
RED and GREEN if in DH+ autobaud detection mode and listening
to the network to determine the baud rate to use.

5.2.3 Off-Line Modes

The following table describes the meaning of LED patterns in the different Off-
Line modes of operation.

LED Pattern

Description of Operation

DH+ and Status

Offline configuration of parameters mode from the serial

menu:  Solid GREEN,  Rest OFF 

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

18

6.0 GW1000 Wiring Diagrams

6.1 Online Cable GW1000-CHA DH+

  

                     

GW1000-CHA DH+

  

Other DH+ Nodes

Note: Clear & Blue might have to be swapped depending on existing DH+ wiring

6.2 Configuration Cable/Online Cable GW1000-CHB RS-232 – No Handshaking

           

GW1000 – CHB

                 PC/OEM Equipment

 


background image

 DataLink Technologies Gateways, Inc.
 Website: 

www.datalink-networks.com

                                            Tel : (604) 632-4278 / (866) 709-6390

 

19

6.3 Online Cable GW1000-CHB RS-232 – With RTS/CTS Handshaking

               

GW1000-CHB

     

            PC/OEM Equipment