CE1N3334en 
2015-03-06 

Building Technologies

 

HVAC Products

 

 

 

 

3

334

 

 

 

 

 

Synco™ 100 

 

 

Immersion Temperature 

Controller 

RLE132 

 

with 3-position output 

 

 

 

 

Immersion temperature controller for basic heating plants. Compact design with 

3-position control. Used as a controller, minimum or maximum limiter.  

Use 

Plant types: 

  Heating zones in heating plants 

  Heating section of ventilation or air conditioning plants 

  Flow temperature in heating plants 

  DHW temperature  

  Heat exchanger control  

  Calorifier control  

Building types: 

  Residential buildings of all types 

  Non-residential buildings of all types 

Used as a limiter:  

  Heating plants controlled by a heating controller with 3-position control, e.g. RVL4…, 

RVP3…, RVP2… 

Devices that can be controlled: 

  Actuators with 3-position control  

 


background image

2/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

Functions 

  Control of the water temperature through 3-position control of a seat or slipper valve  

  Minimum or maximum limitation of the flow or return temperature, or minimum 

limitation of the boiler return temperature 

 

  Outside temperature compensation 

  Remote setpoint adjustment  

  Setpoint changeover via external contact, can be selected to provide temperature 

setback or legionella function  

  Frost protection  

  Load-dependent switching contact (e.g. for pump release)  

  Test mode as a commissioning aid 

Ordering  

When ordering, please give type reference 

RLE132

.  

Equipment combinations  

Actuators must meet the following specification: 

  3-position control 

  Control contacts suited for AC 24…230 V, 2 A  

  Running times:  

 

≥30 s (30 s or 35 s)  

 

≥120 s (120 s, 125 s, 135 s, 150 s or 160 s)  

For auxiliary functions, the following products can be used: 

Type of unit 

Type ref. 

Data Sheet 

Outside sensor (for outside temperature compensation) 

QAC22 

N1811 

Remote setpoint adjuster 

BSG21.1 

N1991 

Scale 0…130 °C for remote setpoint adjuster 

BSG-Z  

N1991 

As a limiter, the RLE132 can be used in connection with the following types of heating 
controllers: 

Type reference 

Data Sheet 

RVL470 

N2522 

RVL471 

N2524 

RVL472 

N2526 

RVP201, RVP211 

N2464 

RVP300 

N2474 

RVP310 

N2475 

RVP320 

N2476 

RVP330 

N2477 

RVP331 

N2478 

Technical design 

When the water temperature deviates from the setpoint, the controller adjusts the 
actuating device until the setpoint is reached again. The neutral zone is ±2 K. The 
controller calculates and stores the running time of the connected actuator. Fully open 
(100 %) corresponds to a heat demand of 100 % (also refer to section “Switching 
contact”).  
The controller provides 2 modes of operation (for details refer to section “Operating 
modes“): 

  Control with ECO 

Main functions 

Other functions 

Mode of operation  

as a controller  

 


background image

3/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

  Control with boost  

The following settings are required: 

  Setpoint 

  Control mode: A choice of 4 PI modes are available to suit the type of controlled 

system (refer to chapter “Mechanical design”)  

  P-band  

 
The control signals of the heating zone controller (RVL4…, RVP3…, RVP2…) are 
passed to the RLE132 which acts as a limiter. 
 
1.  If the temperature (e.g. the boiler return temperature) falls to a level 4 K above the 

minimum limit value, the RLE132 interrupts the OPEN signals of the heating zone 
controller. At the same time, it delivers CLOSE commands in the form of pulses to 
the mixing valve’s actuator until the temperature rises again.  

2.  If the temperature falls to the minimum limit value, the RLE132 delivers a constant 

CLOSE command to the mixing valve’s actuator until the temperature rises again. 

3.  If the temperature rises, the RLE132 releases the positioning commands of the 

heating zone controller.  

 
1.  If the temperature (e.g. the flow temperature) rises to a level 4 K below the 

maximum limit value, the RLE132 interrupts the OPEN signals of the heating zone 
controller. At the same time, it delivers CLOSE commands to the mixing valve’s 
actuator in the form of pulses until the temperature falls again. 

2.  If the temperature reaches the maximum limit value, the RLE132 delivers a 

constant CLOSE command to the mixing valve’s actuator until the temperature falls 
again.  

3.  If the temperature falls, the RLE132 releases the positioning commands of the 

heating zone controller.  

 

When using an outside sensor, the RLE132 provides outside temperature 
compensation. If the outside temperature falls from +15 to –5 °C, the setpoint will be 
continuously raised by 0 K to 26 K. Below an outside temperature of –5 °C, the 
temperature increase will be kept constant.  

 

T

A

  Outside temperature  

Current setpoint  

w

N

  Nominal setpoint  

 
Where the controller is mounted in an inaccessible location, a remote setpoint adjuster 
BSG21.1 can be connected to the RLE132 (terminals R1–M), thus enabling the 
setpoint to be adjusted from a remote location. In this case, the controller’s setpoint 
setting slider must be set to EXT.  
 

 

 

In operating mode 

Control with ECO

, the nominal setpoint is 

reduced

 by closing an 

external potential-free contact across terminals D1–M.  
This ensures energy savings, e.g. through night setback of space heating controlled by 
a time switch. 

 

In operating mode 

Control with boost

, the nominal setpoint is 

raised

 by closing an 

external potential-free contact across terminals D1–M.  

Mode of operation  

as a limiter 

Minimum limitation 

Maximum limitation 

Outside 

temperature 

compensation 

Remote adjustment  

of setpoint 

Operating modes  

Control with ECO  
(setpoint decrease) 

Control with boost  
(setpoint increase) 

 


background image

4/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

This makes possible legionella protection in DHW heating systems. With the help of a 
7-day time switch, the DHW is periodically heated up to the required temperature. 

 

A slider is provided to set the temperature by which the nominal setpoint shall be 
lowered (ECO) or raised (boost). The setting cannot be accessed by the user. 

 

The switching output (terminals Q13–Q14) enables a plant element to be switched 
depending on demand, or a limitation alarm to be generated. The mode of operation 
depends on the operating mode selected on the RLE132:  

  When used as a 

controller

:  

The switching contact makes when there is a heat demand of 5 %. The contact 
breaks, when there is no demand (0 %) for a period of 12 minutes.  

  When used as a 

limiter

:  

The contact makes when the limitation value is reached, and breaks when normal 
operation is resumed.  

 

In test mode, the control is switched off. The setpoint setting knob acts as a positioning unit: 

  If a setting >104 °C is used, the actuating device will open (OPEN command on Y1)  

  If a setting <26 °C is used, the actuating device will close (CLOSE command on Y2)  

The test mode is indicated by an LED.  

Mechanical design  

The controller is designed for mounting into piping. It consists of a housing and cover 
and an immersion rod. The rod contains the sensing element (LG-Ni 1000).  
The housing is made of plastic and accommodates the controller electronics and all 
operating elements, which are accessible only after removing the cover. The front 
carries the setpoint setting slider and an LED for indicating operation: 

  LED lit: normal operation  

  LED flashes: test mode  

 

 

LED 

Block of DIP-switches 

Setting slider for the setpoint increase or 

decrease 

Setting potentiometer for the P-band 

All functions are selected via the DIP switch block which comprises 6 switches:  

Function 

1  2  3  4  5  6  Action  

Operating 

           

Heating with boost; setpoint increase 

 

           

Maximum limitation 

 

           

Minimum limitation  

 

           

Heating with ECO; setpoint decrease  

Integral action time 

   

       

VERY SLOW, T

N

 = 300 s 

 

   

       

SLOW, T

N

 = 180 s 

 

   

       

FAST, T

N

 = 60 s  

 

   

       

MEDIUM, T

N

 = 120 s 

Test mode 

       

   

Test mode 

 

       

   

Normal operation 

Running time of 
actuator 

         

 

>30 s  

         

 

>120 s  

 

Setting  

Switching contact 

Test mode 

 


background image

5/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

For mounting, a protection pocket is provided; the controller is inserted and snaps on.  

Engineering notes 

The controller is supplied complete with Mounting and Installation Instructions. 

Mounting notes  

Ensure that the local safety regulations are complied with. 

Suitable mounting locations are the following, depending on the application:  

  Flow temperature control: 

 

In the heating flow; immediately after the pump if the pump is mounted in the flow 

 

In the heating flow; approximately 1.5 to 2 m after the mixing point if the pump is 
mounted in the return 

  Minimum limitation of the boiler return temperature and maximum limitation of the 

flow temperature:  
1.5 to 2 m after the mixing point 

  DHW temperature control:  

1.5 to 2 m after the mixing point 

  Heat exchanger control:  

As close as possible to the heat exchanger while observing the maximum 
permissible ambient temperature  

To mount the protection pocket, a threaded sleeve must be fitted into the pipe. The 

immersion rod should face the direction of flow. The maximum permissible ambient 

temperature must be observed. 

 

 

Warning! 

No internal line protection for supply lines to external consumers. 

Risk of fire and injury due to short-circuits! 

  Adapt the line diameters as per local regulations to the rated value of the installed 

overcurrent protection device. 

  The AC 230 V mains supply line must have an external circuit breaker with a rated 

current of no more than 10 A. 

 

Commissioning notes  

To check the control wiring, the controller can be switched into test mode so that the 

response of the actuating device can be checked. 

 In case of instability of the control loop, the P-band is to be increased, and/or the 

integral action time selection. If the response of the system is too slow, these values 

are to be reduced. 

 

Disposal 

The devices are considered electronics devices for disposal in terms of European 
Directive 2012/19/EU and may not be disposed of as domestic waste. 

  Dispose of the device via the channels provided for this purpose. 

  Comply with all local and currently applicable laws and regulations. 

 

 

 

 

   

 

 

 

 

 

 


background image

6/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

Technical data  

Operating voltage 

AC 230 V +10% / –15% 

Frequency 

50 / 60 Hz 

Power consumption 

max. 4 VA  

No internal fuse. 

External preliminary protection with max. C 10 A circuit breaker in the supply line 
required under all circumstances. 

Setting range nominal setpoint 

0…130 °C 

Setting range setpoint changeover 

0…50 K  

P-band  

1…50 K 

Integral action time with PI control 

selectable (60 / 120 / 180 / 300 s) 

Control outputs Y1, Y2 

Voltage 
Current 

 
AC 24…230 V 
max. 2 A 

Control outputs Q13–Q14  

Voltage 
Current 

 
AC 24…230 V  
max. 2 A 

Max. cable length copper cable 1.5 mm

For signal input B9

 

For switching input D1 

 
80 m 
80 m 

Contact sensing (input D1–M) 

DC 6…15 V, 3…6 mA 

 

Operation 

Climatic conditions 
Temperature 
Humidity 

 
to IEC 60721-3-3, class 3K5 
0…

+

50 °C 

<

95 % r.h. 

Transport 

Climatic conditions 

Temperature 

Humidity 

 

to IEC 60721-3-2, class 2K3 

25…+70 °C 

<95 % r.h. 

Mechanical conditions 

class 2M2 

 

EU Conformity (CE) 

CE1T3330xx *) 

Degree of protection 

IP65 EN 60529 

Safety class 

II to EN 60730 

Degree of contamination 

normal 

The product environmental declaration CE1E3333en *) contains data on 
environmentally compatible product design and assessments (RoHS compliance, 
materials composition, packaging, environmental benefit, disposal). 
Connection terminals for solid wires or  

stranded wires 

2 × 1.5 mm

2

 or 1 × 2.5 mm

2

 

Sensor  

Sensing element 
Time constant (with protection pocket) 

 
LG-Ni 1000 

 at 0 °C 

25 s 

Protection pocket  

Immersion depth  
Perm. nominal pressure  
Made of 

 
150 mm  
PN10 
brass (Ms63) 

Weight 

0.3 kg 

*) The documents can be downloaded from http://siemens.com/bt/download.

 

Power Supply 

 

Functional Data  

Environmental 

conditions 

Norms and standards 

Environmental 
compatibility 

General 

 


background image

7/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

Connection terminals 

R1 M

Y1

Y2

33

34

G

01

L

N

D1 M

Q13

Q14

F2

F1

N

B9

 

B9  Outside sensor  

D1  Input for setpoint changeover 

F1 

Input for Y1 

F2 

Input for Y2 

L, N  Operating voltage AC 230 V 

Ground 

R1  Input for remote setpoint adjuster 

Q13  Switching contact 

Q14 

Y1  Control output for mixing valve OPEN 

Y2  Control output for mixing valve CLOSED 

Connection diagram  

L

M

N

A

C

 2

30

 V

B9

B9

B1 M

L

N

Y1

D1

M

Y2

N1

33

34

A

01

K1

Y1

Y1

N

Y2

F1

F2

R1

R1

B1

M

Q13

L

N

Q14

M1

 

Used as a controller, flow temperature with outside temperature compensation, remote 
setting unit, setpoint changeover and demand control of a pump  

L

Y1

N

A

C

 2

30

 V

Y2

N3

33

34

A

02

L

N

F1

F2

Y1

Y1

N

Y2

Y1

Y2

L

N

N2

 

Used as a limiter in connection with a heating zone controller (RVL4…, RVP3…, 
RVP2…), e.g. minimum limitation of the boiler return temperature or maximum limitation 
of the boiler flow temperature  

B9 

Outside sensor QAC22 

K1 

External contact (e.g. time switch) 

M1  Pump  

N1  Immersion temperature controller RLE132  

N2  Immersion temperature controller RLE132 as a limiter 

N3  Heating controller RVL4…, RVP3…, RVP2…  

R1  Remote setpoint adjuster BSG21.1 

Y1 

Actuator of heating circuit valve 

 


background image

8/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

Application examples 

33

34

S

01

N1

T

Y1

 

DHW temperature control 

 

33

34

S

02

N1

T

Y1

 

Flow temperature control in a 
heating zone with a common 
flow 

 

33

34

S

03

N3

T

Y1

N2

T

 

Control of a heating zone with 
zone controller RV…, minimum 
limitation of the boiler return 
temperature with RLE132 

 

33

34

S

04

Y1

N1

T

T

F1

 

Heat exchanger control with 2-
port valve in the primary flow 

 

 

33

34

S

05

N3

T

Y1

N2

T

 

Control of a heating zone with 
zone controller RV…, maximum 
limitation of the flow 
temperature with RLE132 

 

33

34

S

06

Y2

N1

T

 

Control of the boiler return 
temperature 

 

F1 

Safety limit thermostat  

N1  Immersion temperature controller RLE132 as a controller 

N2  Immersion temperature controller RLE132 as a limiter 

N3  Heating zone controller RVL4…, RVP3…, RVP2… 

Y1 

Heating circuit mixing valve or primary circuit valve or DHW mixing valve 

Y2 

Mixing valve, boiler return circuit  

 


background image

9/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

Dimensions  

 

Controller with protection pocket 

Dimensions in mm 

 


background image

10/10 

Siemens 

Immersion temperature controller RLE132 

CE1N3334en 

Building Technologies 

 

2015-03-06 

 