PDF User Manual

  1. Home
  2. Manuals
  3. Viessmann VITOCAL 200-S Datasheet

Viessmann VITOCAL 200-S Datasheet

Made by: Viessmann
Type: Datasheet
Category: Heat Pump
Pages: 10
Size: 1.77 MB

 

Download PDF User Manual



Full Text Searchable PDF User Manual



background image

VIESMANN

VITOCAL 200-S

Air/water heat pump, split version

3.0 to 10.6 kW

VITOCAL 200-S   

Type AWB 201.B

Heat pump with electric drive in split design with external and

internal unit.

For central heating and DHW heating in heating systems.

VITOCAL 200-S   

Type AWB-AC 201.B

Equipment level as per type AWB 201.B, with additional active

cooling function plus integral instantaneous heating water

heater.

5822 525 GB

5/2011

Datasheet

For part no. and prices: see pricelist

 


background image

■ Low operating costs through high COP (COP = Coefficient of Per-

formance) to EN 14511: Up to 4.6 (air 7 

°

C/water 35 

°

C) and up to

3.5 (air 2 

°

C/water 35 

°

C). Output control and DC inverter for high

efficiency in partial load operation. 

■ Maximum flow temperature: Up to 55 

°

C at -15 

°

C outside temper-

ature (with reduced output).

■ Weather-proof external unit with evaporator, compressor, expansion

valve and fan.

■ Internal unit with high efficiency heating circuit pump (to Energy

Label A), heat exchanger, 3-way diverter valve, safety assembly and
control unit; for the heating/cooling versions with an integral instan-
taneous heating water heater.

■ Easy to use Vitotronic control unit with plain text and graphic display
■ Highly convenient through reversible system that enables heating

and cooling.

 

EHPA quality seal as proof of the COP for subsidy according
to the German market incentive programme.

Benefits

2

VIESMANN

VITOCAL 200-S

5822 525 GB

 

 


background image

Specification

Vitocal 200-S
Type AWB/AWB-AC

 

201.B04

201.B07

201.B10

201.B13

Output details, heating

to EN 14511 (A2/W35 

°

C, 5 K spread)

 

 

 

 

Rated heating output

kW

3.00

5.60

7.70

10.60

Compressor frequency

Hz

60

65

55

75

Fan speed

rpm

870

650

650

650

Power consumption

kW

0.91

1.73

2.20

3.25

Coefficient of performance 

ε

 (COP) in

heating mode

 

3.27

3.24

3.50

3.26

Output control

kW

1.10 

 3.80

1.30 

 7.70

4.40 

 9.90

5.00 

 11.90

Heating output data

to EN 14511 (A7/W35 

°

C, 5 K spread)

 

 

 

 

Rated heating output

kW

4.50

8.00

10.90

14.60

Compressor frequency

Hz

60

65

55

75

Fan speed

rpm

870

650

650

650

Power consumption

kW

0.97

1.88

2.36

3.40

Coefficient of performance 

ε

 (COP) in

heating mode

 

4.64

4.26

4.62

4.29

Cooling capacity data

to EN 14511 (A35/W7 

°

C, 5 K spread)

 

 

 

 

Rated cooling capacity

kW

3.20

6.20

7.40

9.10

Compressor frequency

Hz

60

65

55

70

Fan speed

rpm

870

650

650

650

Power consumption

kW

1.08

2.40

2.69

3.64

Energy efficiency ratio EER

 

2.96

2.60

2.75

2.50

Output control

kW

1.2 

 3.8

1.6 

 8.0

2.4 

 8.5

2.4 

 10.0

Cooling capacity data

to EN 14511 (A35/W18 

°

C, 5 K spread)

 

 

 

 

Rated cooling capacity

kW

4.20

8.80

10.00

12.60

Compressor frequency

Hz

60

65

55

70

Fan speed

rpm

870

650

650

650

Power consumption

kW

1.13

2.63

2.80

4.20

Energy efficiency ratio EER

 

3.72

3.35

3.57

3.00

Air intake temperature

 

 

 

 

 

Cooling mode

 (type AWB-AC)

 

 

 

 

 

– Min.

°

C

15

15

15

15

– Max.

°

C

45

45

45

45

Heating mode

 (type AWB, AWB-AC)

 

 

 

 

 

– Min.

°

C

15

15

15

15

– Max.

°

C

35

35

35

35

Heating water

at 10 K spread

 

 

 

 

 

Content

l

2.2

2.2

3.2

3.2

Minimum flow rate (always maintain)

l/h

600

820

1200

1380

Max. flow temperature

°

C

55

55

55

55

Electrical values

 

 

 

 

 

External unit

 

 

– Rated voltage, compressor

 

1/N/PE 230 V/50 Hz

– Max. rated current, compressor

A

5

9

10

15

– Starting current, compressor

A

10.5

15

10

10

– Compressor starting current with stalled

armature

A

20

25

25

32

– Starting current (charging DC capaci-

tors)

A

45

< 35

30

30

– Internal fuse/MCB

A

3.5

3.5

3.15

3.15

– IP rating

IP

24

24

24

24

Specification

VITOCAL 200-S

VIESMANN

3

5822 525 GB

 


background image

Type AWB/AWB-AC

 

201.B04

201.B07

201.B10

201.B13

Electrical values

 

 

 

 

 

Internal unit

 

 

Heat pump control unit/PCB

 

 

 

 

 

– Rated voltage, control unit/PCB

 

1/N/PE 230 V/50 Hz

– Fuse protection, power supply

 

1xB16A

– Internal fuse/MCB

 

6.3A (slow)/250 V

Instantaneous heating water heater

Only for type AWB-AC

 

 

 

 

 

– Rated voltage

 

1/N/PE 230 V/50 Hz
3/N/PE 400 V/50 Hz

– Heating output

kW

8.8

8.8

8.8

8.8

– Fuse protection, power supply

 

3xB16A

3xB16A

3xB16A

3xB16A

Electrical power consumption

 

 

 

 

 

– Fan (max.)

W

65

70

130

130

– External unit (max.)

W

3.0

3.6

5.8

5.8

– Secondary pump

W

50

50

70

70

– Control unit/PCB, external unit (max.)

W

150

150

150

150

– Control unit/PCB, internal unit (max.)

W

5

5

5

5

– Max. power, control unit/PCB

W

1000

1000

1000

1000

Refrigerant circuit

 

 

 

 

 

Refrigerant

 

R410A

R410A

R410A

R410A

Fill volume

kg

1.2

2.15

2.95

2.95

Top-up amount for line lengths 

>

12 m to

30 m

g/m

20

60

60

60

Compressor (hermetically sealed)

Type

Rotating piston

Rotating piston

Scroll

Scroll

Permiss. operating pressure

 

 

 

 

 

– High pressure side

bar

MPa

43

4.3

43

4.3

43

4.3

43

4.3

– Low pressure side

bar

MPa

43

4.3

43

4.3

43

4.3

43

4.3

Dimensions

 

 

 

 

 

External unit

 

 

 

 

 

Total length

mm

869

1040

900

900

Total width

mm

290

340

340

340

Total height

mm

610

865

1255

1255

Internal unit

 

 

 

 

 

Total length

mm

450

450

450

450

Total width

mm

360

360

360

360

Total height

mm

905

905

905

905

Total weight

 

 

 

 

 

External unit

kg

43

66

110

110

Internal unit type AWB

kg

34

34

37

37

Internal unit type AWB-AC

kg

38

38

41.5

41.5

Permiss. operating pressure

, secondary

side

bar

MPa

3

0.3

3

0.3

3

0.3

3

0.3

Connections

 

 

 

 

 

Heating water flow

G

1

¼

1

¼

1

¼

1

¼

Heating water return and DHW cylinder
return

G

1

¼

1

¼

1

¼

1

¼

DHW cylinder flow

G

1

¼

1

¼

1

¼

1

¼

Condensate line (external unit)

mm

16 x 1

16 x 1

16 x 1

16 x 1

Liquid line

 

 

 

 

 

– Pipe 

7

mm

6 x 1

10 x 1

10 x 1

10 x 1

– Internal unit

UNF

– External unit

UNF

₁₆

Hot gas line

 

 

 

 

 

– Pipe 

7

mm

12 x 1

16 x 1

16 x 1

16 x 1

– Internal unit

UNF

– External unit

UNF

¾

Refrigerant line lengths

 

 

 

 

 

– Min.

m

3

3

3

3

– Max.

m

20

30

30

30

Sound power of the external unit

*1

Weighted total sound power level at
A7 

°

C (

±

3 K)/W35 

°

C (

±

5 K)

 

 

 

 

 

– At rated heating output

dB(A)

60

62

62

63

*1

Measurements with reference to EN 12102/EN ISO 9614-2

Specification

 (cont.)

4

VIESMANN

VITOCAL 200-S

5822 525 GB

 

 


background image

Internal unit dimensions

905

58

40

360

+

1105

150

AB

/

960

50

360

450

A B

75

147

219

294

369

41

A

Cable entry <42 V

B

Cable entry 400 V~/230 V~, 

>

42 V

Specification

 (cont.)

VITOCAL 200-S

VIESMANN

5

5822 525 GB

 

 


background image

100

1000

100

A

B

A

Cable entry <42 V

B

Cable entry 400 V~/230 V~, 

>

42 V

Hydraulic connections
Symbol

Meaning

Connection

Refrigerant lines from/to the external unit:

7

 connection pipe

UNF thread

– Liquid line

 

10 mm

For type AWB-AC 201.B04, a reduction from 10 to 6 mm is required
downstream from the internal unit connection (reducer 

 to 

₁₆

supplied).

– Hot gas line

 

16 mm

For type AWB-AC 201.B04, a reduction from 16 to 12 mm is
required downstream from the internal unit connection (reducer 

to 

¾

 supplied).

DHW cylinder flow (heating water side)

G 1

¼

+

Heating water return and DHW cylinder return

G 1

¼

Heating water flow

G 1

¼

Specification

 (cont.)

6

VIESMANN

VITOCAL 200-S

5822 525 GB

 

 


background image

External unit dimensions

Type AWB/AWB-AC 201.B04

74

308

290

610

500

40

795

869

Specification

 (cont.)

VITOCAL 200-S

VIESMANN

7

5822 525 GB

 

 


background image

Type AWB/AWB-AC 201.B07

340

950

1040

865

527

378

90

48

Specification

 (cont.)

8

VIESMANN

VITOCAL 200-S

5822 525 GB

 

 


background image

Types AWB/AWB-AC 201.B10 and B13

340

1255

903

705

97

357

357

50

Specification

 (cont.)

VITOCAL 200-S

VIESMANN

9

5822 525 GB

 

 


background image

10

VIESMANN

VITOCAL 200-S

5822 525 GB

Printed on environmentally friendly,

chlorine-free bleached paper

Subject to technical modifications.

Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: info-uk@viessmann.com

 

Viessmann Werke GmbH&Co KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780