Full Text Searchable PDF User Manual
VIESMANN
VITOCAL 200-S
Air/water heat pump, split version
3.0 to 10.6 kW
VITOCAL 200-S
Type AWB 201.B
Heat pump with electric drive in split design with external and
internal unit.
For central heating and DHW heating in heating systems.
VITOCAL 200-S
Type AWB-AC 201.B
Equipment level as per type AWB 201.B, with additional active
cooling function plus integral instantaneous heating water
heater.
5822 525 GB
5/2011
Datasheet
For part no. and prices: see pricelist
■ Low operating costs through high COP (COP = Coefficient of Per-
formance) to EN 14511: Up to 4.6 (air 7
°
C/water 35
°
C) and up to
3.5 (air 2
°
C/water 35
°
C). Output control and DC inverter for high
efficiency in partial load operation.
■ Maximum flow temperature: Up to 55
°
C at -15
°
C outside temper-
ature (with reduced output).
■ Weather-proof external unit with evaporator, compressor, expansion
valve and fan.
■ Internal unit with high efficiency heating circuit pump (to Energy
Label A), heat exchanger, 3-way diverter valve, safety assembly and
control unit; for the heating/cooling versions with an integral instan-
taneous heating water heater.
■ Easy to use Vitotronic control unit with plain text and graphic display
■ Highly convenient through reversible system that enables heating
and cooling.
EHPA quality seal as proof of the COP for subsidy according
to the German market incentive programme.
Benefits
2
VIESMANN
VITOCAL 200-S
5822 525 GB
Specification
Vitocal 200-S
Type AWB/AWB-AC
201.B04
201.B07
201.B10
201.B13
Output details, heating
to EN 14511 (A2/W35
°
C, 5 K spread)
Rated heating output
kW
3.00
5.60
7.70
10.60
Compressor frequency
Hz
60
65
55
75
Fan speed
rpm
870
650
650
650
Power consumption
kW
0.91
1.73
2.20
3.25
Coefficient of performance
ε
(COP) in
heating mode
3.27
3.24
3.50
3.26
Output control
kW
1.10
–
3.80
1.30
–
7.70
4.40
–
9.90
5.00
–
11.90
Heating output data
to EN 14511 (A7/W35
°
C, 5 K spread)
Rated heating output
kW
4.50
8.00
10.90
14.60
Compressor frequency
Hz
60
65
55
75
Fan speed
rpm
870
650
650
650
Power consumption
kW
0.97
1.88
2.36
3.40
Coefficient of performance
ε
(COP) in
heating mode
4.64
4.26
4.62
4.29
Cooling capacity data
to EN 14511 (A35/W7
°
C, 5 K spread)
Rated cooling capacity
kW
3.20
6.20
7.40
9.10
Compressor frequency
Hz
60
65
55
70
Fan speed
rpm
870
650
650
650
Power consumption
kW
1.08
2.40
2.69
3.64
Energy efficiency ratio EER
2.96
2.60
2.75
2.50
Output control
kW
1.2
–
3.8
1.6
–
8.0
2.4
–
8.5
2.4
–
10.0
Cooling capacity data
to EN 14511 (A35/W18
°
C, 5 K spread)
Rated cooling capacity
kW
4.20
8.80
10.00
12.60
Compressor frequency
Hz
60
65
55
70
Fan speed
rpm
870
650
650
650
Power consumption
kW
1.13
2.63
2.80
4.20
Energy efficiency ratio EER
3.72
3.35
3.57
3.00
Air intake temperature
Cooling mode
(type AWB-AC)
– Min.
°
C
15
15
15
15
– Max.
°
C
45
45
45
45
Heating mode
(type AWB, AWB-AC)
– Min.
°
C
–
15
–
15
–
15
–
15
– Max.
°
C
35
35
35
35
Heating water
at 10 K spread
Content
l
2.2
2.2
3.2
3.2
Minimum flow rate (always maintain)
l/h
600
820
1200
1380
Max. flow temperature
°
C
55
55
55
55
Electrical values
External unit
– Rated voltage, compressor
1/N/PE 230 V/50 Hz
– Max. rated current, compressor
A
5
9
10
15
– Starting current, compressor
A
10.5
15
10
10
– Compressor starting current with stalled
armature
A
20
25
25
32
– Starting current (charging DC capaci-
tors)
A
45
< 35
30
30
– Internal fuse/MCB
A
3.5
3.5
3.15
3.15
– IP rating
IP
24
24
24
24
Specification
VITOCAL 200-S
VIESMANN
3
5822 525 GB
Type AWB/AWB-AC
201.B04
201.B07
201.B10
201.B13
Electrical values
Internal unit
Heat pump control unit/PCB
– Rated voltage, control unit/PCB
1/N/PE 230 V/50 Hz
– Fuse protection, power supply
1xB16A
– Internal fuse/MCB
6.3A (slow)/250 V
Instantaneous heating water heater
Only for type AWB-AC
– Rated voltage
1/N/PE 230 V/50 Hz
3/N/PE 400 V/50 Hz
– Heating output
kW
8.8
8.8
8.8
8.8
– Fuse protection, power supply
3xB16A
3xB16A
3xB16A
3xB16A
Electrical power consumption
– Fan (max.)
W
65
70
130
130
– External unit (max.)
W
3.0
3.6
5.8
5.8
– Secondary pump
W
50
50
70
70
– Control unit/PCB, external unit (max.)
W
150
150
150
150
– Control unit/PCB, internal unit (max.)
W
5
5
5
5
– Max. power, control unit/PCB
W
1000
1000
1000
1000
Refrigerant circuit
Refrigerant
R410A
R410A
R410A
R410A
Fill volume
kg
1.2
2.15
2.95
2.95
Top-up amount for line lengths
>
12 m to
≤
30 m
g/m
20
60
60
60
Compressor (hermetically sealed)
Type
Rotating piston
Rotating piston
Scroll
Scroll
Permiss. operating pressure
– High pressure side
bar
MPa
43
4.3
43
4.3
43
4.3
43
4.3
– Low pressure side
bar
MPa
43
4.3
43
4.3
43
4.3
43
4.3
Dimensions
External unit
Total length
mm
869
1040
900
900
Total width
mm
290
340
340
340
Total height
mm
610
865
1255
1255
Internal unit
Total length
mm
450
450
450
450
Total width
mm
360
360
360
360
Total height
mm
905
905
905
905
Total weight
External unit
kg
43
66
110
110
Internal unit type AWB
kg
34
34
37
37
Internal unit type AWB-AC
kg
38
38
41.5
41.5
Permiss. operating pressure
, secondary
side
bar
MPa
3
0.3
3
0.3
3
0.3
3
0.3
Connections
Heating water flow
G
1
¼
1
¼
1
¼
1
¼
Heating water return and DHW cylinder
return
G
1
¼
1
¼
1
¼
1
¼
DHW cylinder flow
G
1
¼
1
¼
1
¼
1
¼
Condensate line (external unit)
mm
16 x 1
16 x 1
16 x 1
16 x 1
Liquid line
– Pipe
7
mm
6 x 1
10 x 1
10 x 1
10 x 1
– Internal unit
UNF
⅝
⅝
⅝
⅝
– External unit
UNF
⁷
⁄
₁₆
⅝
⅝
⅝
Hot gas line
– Pipe
7
mm
12 x 1
16 x 1
16 x 1
16 x 1
– Internal unit
UNF
⅞
⅞
⅞
⅞
– External unit
UNF
¾
⅞
⅞
⅞
Refrigerant line lengths
– Min.
m
3
3
3
3
– Max.
m
20
30
30
30
Sound power of the external unit
*1
Weighted total sound power level at
A7
°
C (
±
3 K)/W35
°
C (
±
5 K)
– At rated heating output
dB(A)
60
62
62
63
*1
Measurements with reference to EN 12102/EN ISO 9614-2
Specification
(cont.)
4
VIESMANN
VITOCAL 200-S
5822 525 GB
Internal unit dimensions
905
58
40
360
+
1105
150
AB
/
960
50
360
450
A B
75
147
219
294
369
41
A
Cable entry <42 V
B
Cable entry 400 V~/230 V~,
>
42 V
Specification
(cont.)
VITOCAL 200-S
VIESMANN
5
5822 525 GB
100
1000
100
A
B
A
Cable entry <42 V
B
Cable entry 400 V~/230 V~,
>
42 V
Hydraulic connections
Symbol
Meaning
Connection
Refrigerant lines from/to the external unit:
7
connection pipe
UNF thread
– Liquid line
10 mm
⅝
For type AWB-AC 201.B04, a reduction from 10 to 6 mm is required
downstream from the internal unit connection (reducer
⅝
to
⁷
⁄
₁₆
supplied).
– Hot gas line
16 mm
⅞
For type AWB-AC 201.B04, a reduction from 16 to 12 mm is
required downstream from the internal unit connection (reducer
⅞
to
¾
supplied).
DHW cylinder flow (heating water side)
G 1
¼
+
Heating water return and DHW cylinder return
G 1
¼
Heating water flow
G 1
¼
Specification
(cont.)
6
VIESMANN
VITOCAL 200-S
5822 525 GB
External unit dimensions
Type AWB/AWB-AC 201.B04
74
308
290
610
500
40
795
869
Specification
(cont.)
VITOCAL 200-S
VIESMANN
7
5822 525 GB
Type AWB/AWB-AC 201.B07
340
950
1040
865
527
378
90
48
Specification
(cont.)
8
VIESMANN
VITOCAL 200-S
5822 525 GB
Types AWB/AWB-AC 201.B10 and B13
340
1255
903
705
97
357
357
50
Specification
(cont.)
VITOCAL 200-S
VIESMANN
9
5822 525 GB
10
VIESMANN
VITOCAL 200-S
5822 525 GB
Printed on environmentally friendly,
chlorine-free bleached paper
Subject to technical modifications.
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: info-uk@viessmann.com
Viessmann Werke GmbH&Co KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780
www.viessmann.com